100 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 1.22V (2.55%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 1.18V (2.45%)
Voltage at Load46.8 VLine Loss: 122.3 W
Max Power & Breaker4.8 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A57.07 V (118.89%)0.0 V94.13 V (196.11%)5706.7 WDrop High
2.5 mm²24 A18 A34.24 V (71.33%)13.8 V56.48 V (117.67%)3424.0 WDrop High
4 mm²32 A25 A21.4 V (44.58%)26.6 V35.3 V (73.54%)2140.0 WDrop High
6 mm²41 A32 A14.27 V (29.72%)33.7 V23.53 V (49.03%)1426.7 WDrop High
10 mm²57 A44 A8.56 V (17.83%)39.4 V14.12 V (29.42%)856.0 WDrop High
16 mm²76 A59 A5.35 V (11.15%)42.6 V8.82 V (18.39%)535.0 WDrop High
25 mm²101 A78 A3.42 V (7.13%)44.6 V5.65 V (11.77%)342.4 WDrop High
35 mm²125 A97 A2.45 V (5.1%)45.6 V4.03 V (8.4%)244.6 WDrop High
50 mm²151 A118 A1.71 V (3.57%)46.3 V2.82 V (5.88%)171.2 W~ ≤5%
70 mm²192 A150 A1.22 V (2.55%)46.8 V2.02 V (4.2%)122.3 W✓ OK (≤3%)
95 mm²232 A181 A0.9 V (1.88%)47.1 V1.49 V (3.1%)90.1 W✓ OK (≤3%)
120 mm²269 A210 A0.71 V (1.49%)47.3 V1.18 V (2.45%)71.3 W✓ OK (≤3%)
150 mm²309 A241 A0.57 V (1.19%)47.4 V0.94 V (1.96%)57.1 W✓ OK (≤3%)
185 mm²353 A275 A0.46 V (0.96%)47.5 V0.76 V (1.59%)46.3 W✓ OK (≤3%)
240 mm²415 A324 A0.36 V (0.74%)47.6 V0.59 V (1.23%)35.7 W✓ OK (≤3%)
300 mm²477 A372 A0.29 V (0.59%)47.7 V0.47 V (0.98%)28.5 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.45%)47.8 V0.35 V (0.74%)21.4 W✓ OK (≤3%)

FAQ — 100 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 100A at 20 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 100A over 20m at 48V (voltage drop: 1.22V or 2.55%).

What is the power capacity of 100A at 48V?

At unity power factor, 100A at 48V supports 4.8 kW with a standard 100A circuit breaker.