⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 16 Ampere ved 25 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 16 A over 25 m ved 400V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 9.88V (2.47%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 9.78V (2.45%)
Voltage at Load390.1 VLine Loss: 273.9 W
Max Power & Breaker11.09 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9.88 V (2.47%)390.1 V16.3 V (4.08%)273.9 W✓ OK (≤3%)
2.5 mm²24 A18 A5.93 V (1.48%)394.1 V9.78 V (2.45%)164.4 W✓ OK (≤3%)
4 mm²32 A25 A3.71 V (0.93%)396.3 V6.11 V (1.53%)102.7 W✓ OK (≤3%)
6 mm²41 A32 A2.47 V (0.62%)397.5 V4.08 V (1.02%)68.5 W✓ OK (≤3%)
10 mm²57 A44 A1.48 V (0.37%)398.5 V2.45 V (0.61%)41.1 W✓ OK (≤3%)
16 mm²76 A59 A0.93 V (0.23%)399.1 V1.53 V (0.38%)25.7 W✓ OK (≤3%)
25 mm²101 A78 A0.59 V (0.15%)399.4 V0.98 V (0.24%)16.4 W✓ OK (≤3%)
35 mm²125 A97 A0.42 V (0.11%)399.6 V0.7 V (0.17%)11.7 W✓ OK (≤3%)
50 mm²151 A118 A0.3 V (0.07%)399.7 V0.49 V (0.12%)8.2 W✓ OK (≤3%)
70 mm²192 A150 A0.21 V (0.05%)399.8 V0.35 V (0.09%)5.9 W✓ OK (≤3%)
95 mm²232 A181 A0.16 V (0.04%)399.8 V0.26 V (0.06%)4.3 W✓ OK (≤3%)
120 mm²269 A210 A0.12 V (0.03%)399.9 V0.2 V (0.05%)3.4 W✓ OK (≤3%)
150 mm²309 A241 A0.1 V (0.02%)399.9 V0.16 V (0.04%)2.7 W✓ OK (≤3%)
185 mm²353 A275 A0.08 V (0.02%)399.9 V0.13 V (0.03%)2.2 W✓ OK (≤3%)
240 mm²415 A324 A0.06 V (0.02%)399.9 V0.1 V (0.03%)1.7 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.01%)400.0 V0.08 V (0.02%)1.4 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)400.0 V0.06 V (0.02%)1.0 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 16 Ampere ved 25 Meter (400V)

Hvilket kabeltværsnit kræves til 16A ved 25 meter (400V)?

Til 16 Ampere over 25 meter ved 400V anbefales 1.5 mm² kobberkabel (spændingsfald 9.88V / 2.47%).

Hvor mange kW svarer 16A ved 400V til?

Det svarer til 11.09 kW med en anbefalet sikring på 16A.