100 Amp Cable Size at 200 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 0.71V (2.97%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.53V (14.71%)
Voltage at Load23.3 VLine Loss: 71.3 W
Max Power & Breaker2.4 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A570.67 V (2377.78%)0.0 V941.33 V (3922.22%)57066.7 WDrop High
2.5 mm²24 A18 A342.4 V (1426.67%)0.0 V564.8 V (2353.33%)34240.0 WDrop High
4 mm²32 A25 A214.0 V (891.67%)0.0 V353.0 V (1470.83%)21400.0 WDrop High
6 mm²41 A32 A142.67 V (594.44%)0.0 V235.33 V (980.56%)14266.7 WDrop High
10 mm²57 A44 A85.6 V (356.67%)0.0 V141.2 V (588.33%)8560.0 WDrop High
16 mm²76 A59 A53.5 V (222.92%)0.0 V88.25 V (367.71%)5350.0 WDrop High
25 mm²101 A78 A34.24 V (142.67%)0.0 V56.48 V (235.33%)3424.0 WDrop High
35 mm²125 A97 A24.46 V (101.9%)0.0 V40.34 V (168.1%)2445.7 WDrop High
50 mm²151 A118 A17.12 V (71.33%)6.9 V28.24 V (117.67%)1712.0 WDrop High
70 mm²192 A150 A12.23 V (50.95%)11.8 V20.17 V (84.05%)1222.9 WDrop High
95 mm²232 A181 A9.01 V (37.54%)15.0 V14.86 V (61.93%)901.1 WDrop High
120 mm²269 A210 A7.13 V (29.72%)16.9 V11.77 V (49.03%)713.3 WDrop High
150 mm²309 A241 A5.71 V (23.78%)18.3 V9.41 V (39.22%)570.7 WDrop High
185 mm²353 A275 A4.63 V (19.28%)19.4 V7.63 V (31.8%)462.7 WDrop High
240 mm²415 A324 A3.57 V (14.86%)20.4 V5.88 V (24.51%)356.7 WDrop High
300 mm²477 A372 A2.85 V (11.89%)21.1 V4.71 V (19.61%)285.3 WDrop High
400 mm²570 A445 A2.14 V (8.92%)21.9 V3.53 V (14.71%)214.0 WDrop High

FAQ — 100 Amp Cable Size at 200 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 100A at 200 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 100A over 200m at 24V (voltage drop: 0.71V or 2.97%).

What is the power capacity of 100A at 24V?

At unity power factor, 100A at 24V supports 2.4 kW with a standard 100A circuit breaker.