125 Amp Cable Size at 100 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.67V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.21V (9.19%)
Voltage at Load23.3 VLine Loss: 83.6 W
Max Power & Breaker3.0 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A356.67 V (1486.11%)0.0 V588.33 V (2451.39%)44583.3 WDrop High
2.5 mm²24 A18 A214.0 V (891.67%)0.0 V353.0 V (1470.83%)26750.0 WDrop High
4 mm²32 A25 A133.75 V (557.29%)0.0 V220.62 V (919.27%)16718.7 WDrop High
6 mm²41 A32 A89.17 V (371.53%)0.0 V147.08 V (612.85%)11145.8 WDrop High
10 mm²57 A44 A53.5 V (222.92%)0.0 V88.25 V (367.71%)6687.5 WDrop High
16 mm²76 A59 A33.44 V (139.32%)0.0 V55.16 V (229.82%)4179.7 WDrop High
25 mm²101 A78 A21.4 V (89.17%)2.6 V35.3 V (147.08%)2675.0 WDrop High
35 mm²125 A97 A15.29 V (63.69%)8.7 V25.21 V (105.06%)1910.7 WDrop High
50 mm²151 A118 A10.7 V (44.58%)13.3 V17.65 V (73.54%)1337.5 WDrop High
70 mm²192 A150 A7.64 V (31.85%)16.4 V12.61 V (52.53%)955.4 WDrop High
95 mm²232 A181 A5.63 V (23.46%)18.4 V9.29 V (38.71%)703.9 WDrop High
120 mm²269 A210 A4.46 V (18.58%)19.5 V7.35 V (30.64%)557.3 WDrop High
150 mm²309 A241 A3.57 V (14.86%)20.4 V5.88 V (24.51%)445.8 WDrop High
185 mm²353 A275 A2.89 V (12.05%)21.1 V4.77 V (19.88%)361.5 WDrop High
240 mm²415 A324 A2.23 V (9.29%)21.8 V3.68 V (15.32%)278.6 WDrop High
300 mm²477 A372 A1.78 V (7.43%)22.2 V2.94 V (12.26%)222.9 WDrop High
400 mm²570 A445 A1.34 V (5.57%)22.7 V2.21 V (9.19%)167.2 WDrop High

FAQ — 125 Amp Cable Size at 100 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 125A at 100 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 125A over 100m at 24V (voltage drop: 0.67V or 2.79%).

What is the power capacity of 125A at 24V?

At unity power factor, 125A at 24V supports 3.0 kW with a standard 125A circuit breaker.