125 Amp Cable Size at 350 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 10.81V (2.7%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 11.15V (2.79%)
Voltage at Load389.2 VLine Loss: 2340.6 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1081.09 V (270.27%)0.0 V1783.29 V (445.82%)234062.5 WDrop High
2.5 mm²24 A18 A648.65 V (162.16%)0.0 V1069.97 V (267.49%)140437.5 WDrop High
4 mm²32 A25 A405.41 V (101.35%)0.0 V668.73 V (167.18%)87773.4 WDrop High
6 mm²41 A32 A270.27 V (67.57%)129.7 V445.82 V (111.46%)58515.6 WDrop High
10 mm²57 A44 A162.16 V (40.54%)237.8 V267.49 V (66.87%)35109.4 WDrop High
16 mm²76 A59 A101.35 V (25.34%)298.6 V167.18 V (41.8%)21943.4 WDrop High
25 mm²101 A78 A64.87 V (16.22%)335.1 V107.0 V (26.75%)14043.7 WDrop High
35 mm²125 A97 A46.33 V (11.58%)353.7 V76.43 V (19.11%)10031.2 WDrop High
50 mm²151 A118 A32.43 V (8.11%)367.6 V53.5 V (13.37%)7021.9 WDrop High
70 mm²192 A150 A23.17 V (5.79%)376.8 V38.21 V (9.55%)5015.6 WDrop High
95 mm²232 A181 A17.07 V (4.27%)382.9 V28.16 V (7.04%)3695.7 W~ ≤5%
120 mm²269 A210 A13.51 V (3.38%)386.5 V22.29 V (5.57%)2925.8 W~ ≤5%
150 mm²309 A241 A10.81 V (2.7%)389.2 V17.83 V (4.46%)2340.6 W✓ OK (≤3%)
185 mm²353 A275 A8.77 V (2.19%)391.2 V14.46 V (3.61%)1897.8 W✓ OK (≤3%)
240 mm²415 A324 A6.76 V (1.69%)393.2 V11.15 V (2.79%)1462.9 W✓ OK (≤3%)
300 mm²477 A372 A5.41 V (1.35%)394.6 V8.92 V (2.23%)1170.3 W✓ OK (≤3%)
400 mm²570 A445 A4.05 V (1.01%)395.9 V6.69 V (1.67%)877.7 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 350 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 125A at 350 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 125A over 350m at 400V (voltage drop: 10.81V or 2.7%).

What is the power capacity of 125A at 400V?

At unity power factor, 125A at 400V supports 86.6 kW with a standard 125A circuit breaker.