15 Amp Cable Size at 30 Meters (400V Three-Phase (IEC European Grid))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 30 m (98.4 ft).
Copper Cable (≤3% Drop)1.5 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 11.01V (2.75%)
Voltage at Load388.9 VLine Loss: 288.9 W
Max Power & Breaker10.39 kW15A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 30m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 11.12 V (2.78%) | 388.9 V | 18.34 V (4.59%) | 288.9 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 6.67 V (1.67%) | 393.3 V | 11.01 V (2.75%) | 173.3 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 4.17 V (1.04%) | 395.8 V | 6.88 V (1.72%) | 108.3 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 2.78 V (0.69%) | 397.2 V | 4.59 V (1.15%) | 72.2 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.67 V (0.42%) | 398.3 V | 2.75 V (0.69%) | 43.3 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.04 V (0.26%) | 399.0 V | 1.72 V (0.43%) | 27.1 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.67 V (0.17%) | 399.3 V | 1.1 V (0.28%) | 17.3 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.48 V (0.12%) | 399.5 V | 0.79 V (0.2%) | 12.4 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.33 V (0.08%) | 399.7 V | 0.55 V (0.14%) | 8.7 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.24 V (0.06%) | 399.8 V | 0.39 V (0.1%) | 6.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.18 V (0.04%) | 399.8 V | 0.29 V (0.07%) | 4.6 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.14 V (0.03%) | 399.9 V | 0.23 V (0.06%) | 3.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.11 V (0.03%) | 399.9 V | 0.18 V (0.05%) | 2.9 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.09 V (0.02%) | 399.9 V | 0.15 V (0.04%) | 2.3 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.07 V (0.02%) | 399.9 V | 0.11 V (0.03%) | 1.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.06 V (0.01%) | 399.9 V | 0.09 V (0.02%) | 1.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.04 V (0.01%) | 400.0 V | 0.07 V (0.02%) | 1.1 W | ✓ OK (≤3%) |
FAQ — 15 Amp Cable Size at 30 Meters (400V Three-Phase (IEC European Grid))
What mm² cable size is required for 15A at 30 meters (400V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 15A over 30m at 400V (voltage drop: 11.12V or 2.78%).
What is the power capacity of 15A at 400V?
At unity power factor, 15A at 400V supports 10.39 kW with a standard 15A circuit breaker.
Related Lengths & Currents (400V)
15A · 5m (400V)15A · 10m (400V)15A · 15m (400V)15A · 20m (400V)15A · 25m (400V)15A · 35m (400V)15A · 40m (400V)15A · 45m (400V)15A · 50m (400V)15A · 60m (400V)15A · 70m (400V)10A · 30m (400V)16A · 30m (400V)20A · 30m (400V)25A · 30m (400V)32A · 30m (400V)40A · 30m (400V)50A · 30m (400V)63A · 30m (400V)80A · 30m (400V)100A · 30m (400V)125A · 30m (400V)160A · 30m (400V)200A · 30m (400V)