16 Amp Cable Size at 15 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 5.93V (1.48%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 5.87V (1.47%)
Voltage at Load394.1 VLine Loss: 164.4 W
Max Power & Breaker11.09 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5.93 V (1.48%)394.1 V9.78 V (2.45%)164.4 W✓ OK (≤3%)
2.5 mm²24 A18 A3.56 V (0.89%)396.4 V5.87 V (1.47%)98.6 W✓ OK (≤3%)
4 mm²32 A25 A2.22 V (0.56%)397.8 V3.67 V (0.92%)61.6 W✓ OK (≤3%)
6 mm²41 A32 A1.48 V (0.37%)398.5 V2.45 V (0.61%)41.1 W✓ OK (≤3%)
10 mm²57 A44 A0.89 V (0.22%)399.1 V1.47 V (0.37%)24.7 W✓ OK (≤3%)
16 mm²76 A59 A0.56 V (0.14%)399.4 V0.92 V (0.23%)15.4 W✓ OK (≤3%)
25 mm²101 A78 A0.36 V (0.09%)399.6 V0.59 V (0.15%)9.9 W✓ OK (≤3%)
35 mm²125 A97 A0.25 V (0.06%)399.7 V0.42 V (0.1%)7.0 W✓ OK (≤3%)
50 mm²151 A118 A0.18 V (0.04%)399.8 V0.29 V (0.07%)4.9 W✓ OK (≤3%)
70 mm²192 A150 A0.13 V (0.03%)399.9 V0.21 V (0.05%)3.5 W✓ OK (≤3%)
95 mm²232 A181 A0.09 V (0.02%)399.9 V0.15 V (0.04%)2.6 W✓ OK (≤3%)
120 mm²269 A210 A0.07 V (0.02%)399.9 V0.12 V (0.03%)2.1 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.01%)399.9 V0.1 V (0.02%)1.6 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.01%)400.0 V0.08 V (0.02%)1.3 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.01%)400.0 V0.06 V (0.02%)1.0 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.01%)400.0 V0.05 V (0.01%)0.8 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.01%)400.0 V0.04 V (0.01%)0.6 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 15 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 16A at 15 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 16A over 15m at 400V (voltage drop: 5.93V or 1.48%).

What is the power capacity of 16A at 400V?

At unity power factor, 16A at 400V supports 11.09 kW with a standard 16A circuit breaker.