175 Amp Cable Size at 20 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 2.14V (0.93%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 2.6V (1.13%)
Voltage at Load227.9 VLine Loss: 374.5 W
Max Power & Breaker40.25 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A99.87 V (43.42%)130.1 V164.73 V (71.62%)17476.7 WDrop High
2.5 mm²24 A18 A59.92 V (26.05%)170.1 V98.84 V (42.97%)10486.0 WDrop High
4 mm²32 A25 A37.45 V (16.28%)192.6 V61.77 V (26.86%)6553.8 WDrop High
6 mm²41 A32 A24.97 V (10.86%)205.0 V41.18 V (17.91%)4369.2 WDrop High
10 mm²57 A44 A14.98 V (6.51%)215.0 V24.71 V (10.74%)2621.5 WDrop High
16 mm²76 A59 A9.36 V (4.07%)220.6 V15.44 V (6.71%)1638.4 WDrop High
25 mm²101 A78 A5.99 V (2.61%)224.0 V9.88 V (4.3%)1048.6 WDrop High
35 mm²125 A97 A4.28 V (1.86%)225.7 V7.06 V (3.07%)749.0 WDrop High
50 mm²151 A118 A3.0 V (1.3%)227.0 V4.94 V (2.15%)524.3 WDrop High
70 mm²192 A150 A2.14 V (0.93%)227.9 V3.53 V (1.53%)374.5 W✓ OK (≤3%)
95 mm²232 A181 A1.58 V (0.69%)228.4 V2.6 V (1.13%)275.9 W✓ OK (≤3%)
120 mm²269 A210 A1.25 V (0.54%)228.8 V2.06 V (0.9%)218.5 W✓ OK (≤3%)
150 mm²309 A241 A1.0 V (0.43%)229.0 V1.65 V (0.72%)174.8 W✓ OK (≤3%)
185 mm²353 A275 A0.81 V (0.35%)229.2 V1.34 V (0.58%)141.7 W✓ OK (≤3%)
240 mm²415 A324 A0.62 V (0.27%)229.4 V1.03 V (0.45%)109.2 W✓ OK (≤3%)
300 mm²477 A372 A0.5 V (0.22%)229.5 V0.82 V (0.36%)87.4 W✓ OK (≤3%)
400 mm²570 A445 A0.37 V (0.16%)229.6 V0.62 V (0.27%)65.5 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 20 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 175A at 20 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 175A over 20m at 230V (voltage drop: 2.14V or 0.93%).

What is the power capacity of 175A at 230V?

At unity power factor, 175A at 230V supports 40.25 kW with a standard 175A circuit breaker.