200 Amp Cable Size at 10 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 0.9V (0.39%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 1.18V (0.51%)
Voltage at Load229.1 VLine Loss: 180.2 W
Max Power & Breaker46.0 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A57.07 V (24.81%)172.9 V94.13 V (40.93%)11413.3 WDrop High
2.5 mm²24 A18 A34.24 V (14.89%)195.8 V56.48 V (24.56%)6848.0 WDrop High
4 mm²32 A25 A21.4 V (9.3%)208.6 V35.3 V (15.35%)4280.0 WDrop High
6 mm²41 A32 A14.27 V (6.2%)215.7 V23.53 V (10.23%)2853.3 WDrop High
10 mm²57 A44 A8.56 V (3.72%)221.4 V14.12 V (6.14%)1712.0 WDrop High
16 mm²76 A59 A5.35 V (2.33%)224.7 V8.82 V (3.84%)1070.0 WDrop High
25 mm²101 A78 A3.42 V (1.49%)226.6 V5.65 V (2.46%)684.8 WDrop High
35 mm²125 A97 A2.45 V (1.06%)227.6 V4.03 V (1.75%)489.1 WDrop High
50 mm²151 A118 A1.71 V (0.74%)228.3 V2.82 V (1.23%)342.4 WDrop High
70 mm²192 A150 A1.22 V (0.53%)228.8 V2.02 V (0.88%)244.6 WDrop High
95 mm²232 A181 A0.9 V (0.39%)229.1 V1.49 V (0.65%)180.2 W✓ OK (≤3%)
120 mm²269 A210 A0.71 V (0.31%)229.3 V1.18 V (0.51%)142.7 W✓ OK (≤3%)
150 mm²309 A241 A0.57 V (0.25%)229.4 V0.94 V (0.41%)114.1 W✓ OK (≤3%)
185 mm²353 A275 A0.46 V (0.2%)229.5 V0.76 V (0.33%)92.5 W✓ OK (≤3%)
240 mm²415 A324 A0.36 V (0.16%)229.6 V0.59 V (0.26%)71.3 W✓ OK (≤3%)
300 mm²477 A372 A0.29 V (0.12%)229.7 V0.47 V (0.2%)57.1 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.09%)229.8 V0.35 V (0.15%)42.8 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 10 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 200A at 10 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 200A over 10m at 230V (voltage drop: 0.9V or 0.39%).

What is the power capacity of 200A at 230V?

At unity power factor, 200A at 230V supports 46.0 kW with a standard 200A circuit breaker.