200 Amp Cable Size at 20 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 1.56V (0.39%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 2.04V (0.51%)
Voltage at Load398.4 VLine Loss: 540.6 W
Max Power & Breaker138.56 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A98.84 V (24.71%)301.2 V163.04 V (40.76%)34240.0 WDrop High
2.5 mm²24 A18 A59.31 V (14.83%)340.7 V97.83 V (24.46%)20544.0 WDrop High
4 mm²32 A25 A37.07 V (9.27%)362.9 V61.14 V (15.29%)12840.0 WDrop High
6 mm²41 A32 A24.71 V (6.18%)375.3 V40.76 V (10.19%)8560.0 WDrop High
10 mm²57 A44 A14.83 V (3.71%)385.2 V24.46 V (6.11%)5136.0 WDrop High
16 mm²76 A59 A9.27 V (2.32%)390.7 V15.29 V (3.82%)3210.0 WDrop High
25 mm²101 A78 A5.93 V (1.48%)394.1 V9.78 V (2.45%)2054.4 WDrop High
35 mm²125 A97 A4.24 V (1.06%)395.8 V6.99 V (1.75%)1467.4 WDrop High
50 mm²151 A118 A2.97 V (0.74%)397.0 V4.89 V (1.22%)1027.2 WDrop High
70 mm²192 A150 A2.12 V (0.53%)397.9 V3.49 V (0.87%)733.7 WDrop High
95 mm²232 A181 A1.56 V (0.39%)398.4 V2.57 V (0.64%)540.6 W✓ OK (≤3%)
120 mm²269 A210 A1.24 V (0.31%)398.8 V2.04 V (0.51%)428.0 W✓ OK (≤3%)
150 mm²309 A241 A0.99 V (0.25%)399.0 V1.63 V (0.41%)342.4 W✓ OK (≤3%)
185 mm²353 A275 A0.8 V (0.2%)399.2 V1.32 V (0.33%)277.6 W✓ OK (≤3%)
240 mm²415 A324 A0.62 V (0.15%)399.4 V1.02 V (0.25%)214.0 W✓ OK (≤3%)
300 mm²477 A372 A0.49 V (0.12%)399.5 V0.82 V (0.2%)171.2 W✓ OK (≤3%)
400 mm²570 A445 A0.37 V (0.09%)399.6 V0.61 V (0.15%)128.4 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 20 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 200A at 20 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 200A over 20m at 400V (voltage drop: 1.56V or 0.39%).

What is the power capacity of 200A at 400V?

At unity power factor, 200A at 400V supports 138.56 kW with a standard 200A circuit breaker.