⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

200 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 0.45V (0.94%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 0.59V (1.23%)
Voltage at Load47.5 VLine Loss: 90.1 W
Max Power & Breaker9.6 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A28.53 V (59.44%)19.5 V47.07 V (98.06%)5706.7 WDrop High
2.5 mm²24 A18 A17.12 V (35.67%)30.9 V28.24 V (58.83%)3424.0 WDrop High
4 mm²32 A25 A10.7 V (22.29%)37.3 V17.65 V (36.77%)2140.0 WDrop High
6 mm²41 A32 A7.13 V (14.86%)40.9 V11.77 V (24.51%)1426.7 WDrop High
10 mm²57 A44 A4.28 V (8.92%)43.7 V7.06 V (14.71%)856.0 WDrop High
16 mm²76 A59 A2.67 V (5.57%)45.3 V4.41 V (9.19%)535.0 WDrop High
25 mm²101 A78 A1.71 V (3.57%)46.3 V2.82 V (5.88%)342.4 WDrop High
35 mm²125 A97 A1.22 V (2.55%)46.8 V2.02 V (4.2%)244.6 WDrop High
50 mm²151 A118 A0.86 V (1.78%)47.1 V1.41 V (2.94%)171.2 WDrop High
70 mm²192 A150 A0.61 V (1.27%)47.4 V1.01 V (2.1%)122.3 WDrop High
95 mm²232 A181 A0.45 V (0.94%)47.5 V0.74 V (1.55%)90.1 W✓ OK (≤3%)
120 mm²269 A210 A0.36 V (0.74%)47.6 V0.59 V (1.23%)71.3 W✓ OK (≤3%)
150 mm²309 A241 A0.29 V (0.59%)47.7 V0.47 V (0.98%)57.1 W✓ OK (≤3%)
185 mm²353 A275 A0.23 V (0.48%)47.8 V0.38 V (0.8%)46.3 W✓ OK (≤3%)
240 mm²415 A324 A0.18 V (0.37%)47.8 V0.29 V (0.61%)35.7 W✓ OK (≤3%)
300 mm²477 A372 A0.14 V (0.3%)47.9 V0.24 V (0.49%)28.5 W✓ OK (≤3%)
400 mm²570 A445 A0.11 V (0.22%)47.9 V0.18 V (0.37%)21.4 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 200A at 5 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 200A over 5m at 48V (voltage drop: 0.45V or 0.94%).

What is the power capacity of 200A at 48V?

At unity power factor, 200A at 48V supports 9.6 kW with a standard 200A circuit breaker.