⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

225 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 6.02V (2.62%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.93V (4.32%)
Voltage at Load224.0 VLine Loss: 1354.2 W
Max Power & Breaker51.75 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1605.0 V (697.83%)0.0 V2647.5 V (1151.09%)361125.0 WDrop High
2.5 mm²24 A18 A963.0 V (418.7%)0.0 V1588.5 V (690.65%)216675.0 WDrop High
4 mm²32 A25 A601.88 V (261.68%)0.0 V992.81 V (431.66%)135421.9 WDrop High
6 mm²41 A32 A401.25 V (174.46%)0.0 V661.88 V (287.77%)90281.2 WDrop High
10 mm²57 A44 A240.75 V (104.67%)0.0 V397.12 V (172.66%)54168.7 WDrop High
16 mm²76 A59 A150.47 V (65.42%)79.5 V248.2 V (107.91%)33855.5 WDrop High
25 mm²101 A78 A96.3 V (41.87%)133.7 V158.85 V (69.07%)21667.5 WDrop High
35 mm²125 A97 A68.79 V (29.91%)161.2 V113.46 V (49.33%)15476.8 WDrop High
50 mm²151 A118 A48.15 V (20.93%)181.8 V79.42 V (34.53%)10833.8 WDrop High
70 mm²192 A150 A34.39 V (14.95%)195.6 V56.73 V (24.67%)7738.4 WDrop High
95 mm²232 A181 A25.34 V (11.02%)204.7 V41.8 V (18.18%)5702.0 WDrop High
120 mm²269 A210 A20.06 V (8.72%)209.9 V33.09 V (14.39%)4514.1 WDrop High
150 mm²309 A241 A16.05 V (6.98%)213.9 V26.47 V (11.51%)3611.2 WDrop High
185 mm²353 A275 A13.01 V (5.66%)217.0 V21.47 V (9.33%)2928.0 WDrop High
240 mm²415 A324 A10.03 V (4.36%)220.0 V16.55 V (7.19%)2257.0 W~ ≤5%
300 mm²477 A372 A8.03 V (3.49%)222.0 V13.24 V (5.76%)1805.6 W~ ≤5%
400 mm²570 A445 A6.02 V (2.62%)224.0 V9.93 V (4.32%)1354.2 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 225A at 250 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 225A over 250m at 230V (voltage drop: 6.02V or 2.62%).

What is the power capacity of 225A at 230V?

At unity power factor, 225A at 230V supports 51.75 kW with a standard 225A circuit breaker.