250 Amp Cable Size at 200 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 10.02V (2.5%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 10.19V (2.55%)
Voltage at Load390.0 VLine Loss: 4337.8 W
Max Power & Breaker173.21 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1235.53 V (308.88%)0.0 V2038.05 V (509.51%)535000.0 WDrop High
2.5 mm²24 A18 A741.32 V (185.33%)0.0 V1222.83 V (305.71%)321000.0 WDrop High
4 mm²32 A25 A463.32 V (115.83%)0.0 V764.27 V (191.07%)200625.0 WDrop High
6 mm²41 A32 A308.88 V (77.22%)91.1 V509.51 V (127.38%)133750.0 WDrop High
10 mm²57 A44 A185.33 V (46.33%)214.7 V305.71 V (76.43%)80250.0 WDrop High
16 mm²76 A59 A115.83 V (28.96%)284.2 V191.07 V (47.77%)50156.2 WDrop High
25 mm²101 A78 A74.13 V (18.53%)325.9 V122.28 V (30.57%)32100.0 WDrop High
35 mm²125 A97 A52.95 V (13.24%)347.0 V87.34 V (21.84%)22928.6 WDrop High
50 mm²151 A118 A37.07 V (9.27%)362.9 V61.14 V (15.29%)16050.0 WDrop High
70 mm²192 A150 A26.48 V (6.62%)373.5 V43.67 V (10.92%)11464.3 WDrop High
95 mm²232 A181 A19.51 V (4.88%)380.5 V32.18 V (8.04%)8447.4 WDrop High
120 mm²269 A210 A15.44 V (3.86%)384.6 V25.48 V (6.37%)6687.5 W~ ≤5%
150 mm²309 A241 A12.36 V (3.09%)387.6 V20.38 V (5.1%)5350.0 W~ ≤5%
185 mm²353 A275 A10.02 V (2.5%)390.0 V16.52 V (4.13%)4337.8 W✓ OK (≤3%)
240 mm²415 A324 A7.72 V (1.93%)392.3 V12.74 V (3.18%)3343.7 W✓ OK (≤3%)
300 mm²477 A372 A6.18 V (1.54%)393.8 V10.19 V (2.55%)2675.0 W✓ OK (≤3%)
400 mm²570 A445 A4.63 V (1.16%)395.4 V7.64 V (1.91%)2006.2 W✓ OK (≤3%)

FAQ — 250 Amp Cable Size at 200 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 250A at 200 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 250A over 200m at 400V (voltage drop: 10.02V or 2.5%).

What is the power capacity of 250A at 400V?

At unity power factor, 250A at 400V supports 173.21 kW with a standard 250A circuit breaker.