⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

250 Amp Cable Size at 500 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 11.58V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 19.11V (4.78%)
Voltage at Load388.4 VLine Loss: 5015.6 W
Max Power & Breaker173.21 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3088.82 V (772.21%)0.0 V5095.12 V (1273.78%)1337500.0 WDrop High
2.5 mm²24 A18 A1853.29 V (463.32%)0.0 V3057.07 V (764.27%)802500.0 WDrop High
4 mm²32 A25 A1158.31 V (289.58%)0.0 V1910.67 V (477.67%)501562.5 WDrop High
6 mm²41 A32 A772.21 V (193.05%)0.0 V1273.78 V (318.44%)334375.0 WDrop High
10 mm²57 A44 A463.32 V (115.83%)0.0 V764.27 V (191.07%)200625.0 WDrop High
16 mm²76 A59 A289.58 V (72.39%)110.4 V477.67 V (119.42%)125390.6 WDrop High
25 mm²101 A78 A185.33 V (46.33%)214.7 V305.71 V (76.43%)80250.0 WDrop High
35 mm²125 A97 A132.38 V (33.09%)267.6 V218.36 V (54.59%)57321.4 WDrop High
50 mm²151 A118 A92.66 V (23.17%)307.3 V152.85 V (38.21%)40125.0 WDrop High
70 mm²192 A150 A66.19 V (16.55%)333.8 V109.18 V (27.3%)28660.7 WDrop High
95 mm²232 A181 A48.77 V (12.19%)351.2 V80.45 V (20.11%)21118.4 WDrop High
120 mm²269 A210 A38.61 V (9.65%)361.4 V63.69 V (15.92%)16718.8 WDrop High
150 mm²309 A241 A30.89 V (7.72%)369.1 V50.95 V (12.74%)13375.0 WDrop High
185 mm²353 A275 A25.04 V (6.26%)375.0 V41.31 V (10.33%)10844.6 WDrop High
240 mm²415 A324 A19.31 V (4.83%)380.7 V31.84 V (7.96%)8359.4 W~ ≤5%
300 mm²477 A372 A15.44 V (3.86%)384.6 V25.48 V (6.37%)6687.5 W~ ≤5%
400 mm²570 A445 A11.58 V (2.9%)388.4 V19.11 V (4.78%)5015.6 W✓ OK (≤3%)

FAQ — 250 Amp Cable Size at 500 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 250A at 500 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 250A over 500m at 400V (voltage drop: 11.58V or 2.9%).

What is the power capacity of 250A at 400V?

At unity power factor, 250A at 400V supports 173.21 kW with a standard 250A circuit breaker.