32 Amp Cable Size at 120 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 1.37V (2.85%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 1.13V (2.35%)
Voltage at Load46.6 VLine Loss: 43.8 W
Max Power & Breaker1.54 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A109.57 V (228.27%)0.0 V180.74 V (376.53%)3506.2 WDrop High
2.5 mm²24 A18 A65.74 V (136.96%)0.0 V108.44 V (225.92%)2103.7 WDrop High
4 mm²32 A25 A41.09 V (85.6%)6.9 V67.78 V (141.2%)1314.8 WDrop High
6 mm²41 A32 A27.39 V (57.07%)20.6 V45.18 V (94.13%)876.5 WDrop High
10 mm²57 A44 A16.44 V (34.24%)31.6 V27.11 V (56.48%)525.9 WDrop High
16 mm²76 A59 A10.27 V (21.4%)37.7 V16.94 V (35.3%)328.7 WDrop High
25 mm²101 A78 A6.57 V (13.7%)41.4 V10.84 V (22.59%)210.4 WDrop High
35 mm²125 A97 A4.7 V (9.78%)43.3 V7.75 V (16.14%)150.3 WDrop High
50 mm²151 A118 A3.29 V (6.85%)44.7 V5.42 V (11.3%)105.2 WDrop High
70 mm²192 A150 A2.35 V (4.89%)45.7 V3.87 V (8.07%)75.1 W~ ≤5%
95 mm²232 A181 A1.73 V (3.6%)46.3 V2.85 V (5.95%)55.4 W~ ≤5%
120 mm²269 A210 A1.37 V (2.85%)46.6 V2.26 V (4.71%)43.8 W✓ OK (≤3%)
150 mm²309 A241 A1.1 V (2.28%)46.9 V1.81 V (3.77%)35.1 W✓ OK (≤3%)
185 mm²353 A275 A0.89 V (1.85%)47.1 V1.47 V (3.05%)28.4 W✓ OK (≤3%)
240 mm²415 A324 A0.68 V (1.43%)47.3 V1.13 V (2.35%)21.9 W✓ OK (≤3%)
300 mm²477 A372 A0.55 V (1.14%)47.5 V0.9 V (1.88%)17.5 W✓ OK (≤3%)
400 mm²570 A445 A0.41 V (0.86%)47.6 V0.68 V (1.41%)13.1 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 120 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 32A at 120 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 32A over 120m at 48V (voltage drop: 1.37V or 2.85%).

What is the power capacity of 32A at 48V?

At unity power factor, 32A at 48V supports 1.54 kW with a standard 32A circuit breaker.