⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

32 Amp Cable Size at 40 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 11.86V (2.97%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 7.83V (1.96%)
Voltage at Load388.1 VLine Loss: 657.4 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A31.63 V (7.91%)368.4 V52.17 V (13.04%)1753.1 WDrop High
2.5 mm²24 A18 A18.98 V (4.74%)381.0 V31.3 V (7.83%)1051.9 WDrop High
4 mm²32 A25 A11.86 V (2.97%)388.1 V19.57 V (4.89%)657.4 W✓ OK (≤3%)
6 mm²41 A32 A7.91 V (1.98%)392.1 V13.04 V (3.26%)438.3 W✓ OK (≤3%)
10 mm²57 A44 A4.74 V (1.19%)395.3 V7.83 V (1.96%)263.0 W✓ OK (≤3%)
16 mm²76 A59 A2.97 V (0.74%)397.0 V4.89 V (1.22%)164.4 W✓ OK (≤3%)
25 mm²101 A78 A1.9 V (0.47%)398.1 V3.13 V (0.78%)105.2 W✓ OK (≤3%)
35 mm²125 A97 A1.36 V (0.34%)398.6 V2.24 V (0.56%)75.1 W✓ OK (≤3%)
50 mm²151 A118 A0.95 V (0.24%)399.1 V1.57 V (0.39%)52.6 W✓ OK (≤3%)
70 mm²192 A150 A0.68 V (0.17%)399.3 V1.12 V (0.28%)37.6 W✓ OK (≤3%)
95 mm²232 A181 A0.5 V (0.12%)399.5 V0.82 V (0.21%)27.7 W✓ OK (≤3%)
120 mm²269 A210 A0.4 V (0.1%)399.6 V0.65 V (0.16%)21.9 W✓ OK (≤3%)
150 mm²309 A241 A0.32 V (0.08%)399.7 V0.52 V (0.13%)17.5 W✓ OK (≤3%)
185 mm²353 A275 A0.26 V (0.06%)399.7 V0.42 V (0.11%)14.2 W✓ OK (≤3%)
240 mm²415 A324 A0.2 V (0.05%)399.8 V0.33 V (0.08%)11.0 W✓ OK (≤3%)
300 mm²477 A372 A0.16 V (0.04%)399.8 V0.26 V (0.07%)8.8 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.03%)399.9 V0.2 V (0.05%)6.6 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 40 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 32A at 40 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 32A over 40m at 400V (voltage drop: 11.86V or 2.97%).

What is the power capacity of 32A at 400V?

At unity power factor, 32A at 400V supports 22.17 kW with a standard 32A circuit breaker.