350 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.68V (2.04%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 15.44V (6.71%)
Voltage at Load225.3 VLine Loss: 1638.5 W
Max Power & Breaker80.5 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2496.67 V (1085.51%)0.0 V4118.33 V (1790.58%)873833.3 WDrop High
2.5 mm²24 A18 A1498.0 V (651.3%)0.0 V2471.0 V (1074.35%)524300.0 WDrop High
4 mm²32 A25 A936.25 V (407.07%)0.0 V1544.37 V (671.47%)327687.5 WDrop High
6 mm²41 A32 A624.17 V (271.38%)0.0 V1029.58 V (447.64%)218458.3 WDrop High
10 mm²57 A44 A374.5 V (162.83%)0.0 V617.75 V (268.59%)131075.0 WDrop High
16 mm²76 A59 A234.06 V (101.77%)0.0 V386.09 V (167.87%)81921.9 WDrop High
25 mm²101 A78 A149.8 V (65.13%)80.2 V247.1 V (107.43%)52430.0 WDrop High
35 mm²125 A97 A107.0 V (46.52%)123.0 V176.5 V (76.74%)37450.0 WDrop High
50 mm²151 A118 A74.9 V (32.57%)155.1 V123.55 V (53.72%)26215.0 WDrop High
70 mm²192 A150 A53.5 V (23.26%)176.5 V88.25 V (38.37%)18725.0 WDrop High
95 mm²232 A181 A39.42 V (17.14%)190.6 V65.03 V (28.27%)13797.4 WDrop High
120 mm²269 A210 A31.21 V (13.57%)198.8 V51.48 V (22.38%)10922.9 WDrop High
150 mm²309 A241 A24.97 V (10.86%)205.0 V41.18 V (17.91%)8738.3 WDrop High
185 mm²353 A275 A20.24 V (8.8%)209.8 V33.39 V (14.52%)7085.1 WDrop High
240 mm²415 A324 A15.6 V (6.78%)214.4 V25.74 V (11.19%)5461.5 WDrop High
300 mm²477 A372 A12.48 V (5.43%)217.5 V20.59 V (8.95%)4369.2 WDrop High
400 mm²570 A445 A9.36 V (4.07%)220.6 V15.44 V (6.71%)3276.9 W~ ≤5%

FAQ — 350 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 350A at 250 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 350A over 250m at 230V (voltage drop: 4.68V or 2.04%).

What is the power capacity of 350A at 230V?

At unity power factor, 350A at 230V supports 80.5 kW with a standard 350A circuit breaker.