375 Amp Cable Size at 45 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 2.61V (0.65%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.58V (0.64%)
Voltage at Load397.4 VLine Loss: 1692.8 W
Max Power & Breaker259.81 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A416.99 V (104.25%)0.0 V687.84 V (171.96%)270843.8 WDrop High
2.5 mm²24 A18 A250.19 V (62.55%)149.8 V412.7 V (103.18%)162506.2 WDrop High
4 mm²32 A25 A156.37 V (39.09%)243.6 V257.94 V (64.49%)101566.4 WDrop High
6 mm²41 A32 A104.25 V (26.06%)295.8 V171.96 V (42.99%)67710.9 WDrop High
10 mm²57 A44 A62.55 V (15.64%)337.5 V103.18 V (25.79%)40626.6 WDrop High
16 mm²76 A59 A39.09 V (9.77%)360.9 V64.49 V (16.12%)25391.6 WDrop High
25 mm²101 A78 A25.02 V (6.25%)375.0 V41.27 V (10.32%)16250.6 WDrop High
35 mm²125 A97 A17.87 V (4.47%)382.1 V29.48 V (7.37%)11607.6 WDrop High
50 mm²151 A118 A12.51 V (3.13%)387.5 V20.64 V (5.16%)8125.3 WDrop High
70 mm²192 A150 A8.94 V (2.23%)391.1 V14.74 V (3.68%)5803.8 WDrop High
95 mm²232 A181 A6.58 V (1.65%)393.4 V10.86 V (2.72%)4276.5 WDrop High
120 mm²269 A210 A5.21 V (1.3%)394.8 V8.6 V (2.15%)3385.5 WDrop High
150 mm²309 A241 A4.17 V (1.04%)395.8 V6.88 V (1.72%)2708.4 WDrop High
185 mm²353 A275 A3.38 V (0.85%)396.6 V5.58 V (1.39%)2196.0 WDrop High
240 mm²415 A324 A2.61 V (0.65%)397.4 V4.3 V (1.07%)1692.8 W✓ OK (≤3%)
300 mm²477 A372 A2.08 V (0.52%)397.9 V3.44 V (0.86%)1354.2 W✓ OK (≤3%)
400 mm²570 A445 A1.56 V (0.39%)398.4 V2.58 V (0.64%)1015.7 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 45 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 375A at 45 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 45m at 400V (voltage drop: 2.61V or 0.65%).

What is the power capacity of 375A at 400V?

At unity power factor, 375A at 400V supports 259.81 kW with a standard 400A circuit breaker.