40 Amp Cable Size at 50 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 7.41V (1.85%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 7.64V (1.91%)
Voltage at Load392.6 VLine Loss: 513.6 W
Max Power & Breaker27.71 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A49.42 V (12.36%)350.6 V81.52 V (20.38%)3424.0 WDrop High
2.5 mm²24 A18 A29.65 V (7.41%)370.3 V48.91 V (12.23%)2054.4 WDrop High
4 mm²32 A25 A18.53 V (4.63%)381.5 V30.57 V (7.64%)1284.0 WDrop High
6 mm²41 A32 A12.36 V (3.09%)387.6 V20.38 V (5.1%)856.0 W~ ≤5%
10 mm²57 A44 A7.41 V (1.85%)392.6 V12.23 V (3.06%)513.6 W✓ OK (≤3%)
16 mm²76 A59 A4.63 V (1.16%)395.4 V7.64 V (1.91%)321.0 W✓ OK (≤3%)
25 mm²101 A78 A2.97 V (0.74%)397.0 V4.89 V (1.22%)205.4 W✓ OK (≤3%)
35 mm²125 A97 A2.12 V (0.53%)397.9 V3.49 V (0.87%)146.7 W✓ OK (≤3%)
50 mm²151 A118 A1.48 V (0.37%)398.5 V2.45 V (0.61%)102.7 W✓ OK (≤3%)
70 mm²192 A150 A1.06 V (0.26%)398.9 V1.75 V (0.44%)73.4 W✓ OK (≤3%)
95 mm²232 A181 A0.78 V (0.2%)399.2 V1.29 V (0.32%)54.1 W✓ OK (≤3%)
120 mm²269 A210 A0.62 V (0.15%)399.4 V1.02 V (0.25%)42.8 W✓ OK (≤3%)
150 mm²309 A241 A0.49 V (0.12%)399.5 V0.82 V (0.2%)34.2 W✓ OK (≤3%)
185 mm²353 A275 A0.4 V (0.1%)399.6 V0.66 V (0.17%)27.8 W✓ OK (≤3%)
240 mm²415 A324 A0.31 V (0.08%)399.7 V0.51 V (0.13%)21.4 W✓ OK (≤3%)
300 mm²477 A372 A0.25 V (0.06%)399.8 V0.41 V (0.1%)17.1 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.05%)399.8 V0.31 V (0.08%)12.8 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 50 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 40A at 50 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 40A over 50m at 400V (voltage drop: 7.41V or 1.85%).

What is the power capacity of 40A at 400V?

At unity power factor, 40A at 400V supports 27.71 kW with a standard 40A circuit breaker.