400 Amp Cable Size at 120 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 7.41V (1.85%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.34V (1.83%)
Voltage at Load392.6 VLine Loss: 5136.0 W
Max Power & Breaker277.13 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1186.11 V (296.53%)0.0 V1956.52 V (489.13%)821760.0 WDrop High
2.5 mm²24 A18 A711.67 V (177.92%)0.0 V1173.91 V (293.48%)493056.0 WDrop High
4 mm²32 A25 A444.79 V (111.2%)0.0 V733.7 V (183.42%)308160.0 WDrop High
6 mm²41 A32 A296.53 V (74.13%)103.5 V489.13 V (122.28%)205440.0 WDrop High
10 mm²57 A44 A177.92 V (44.48%)222.1 V293.48 V (73.37%)123264.0 WDrop High
16 mm²76 A59 A111.2 V (27.8%)288.8 V183.42 V (45.86%)77040.0 WDrop High
25 mm²101 A78 A71.17 V (17.79%)328.8 V117.39 V (29.35%)49305.6 WDrop High
35 mm²125 A97 A50.83 V (12.71%)349.2 V83.85 V (20.96%)35218.3 WDrop High
50 mm²151 A118 A35.58 V (8.9%)364.4 V58.7 V (14.67%)24652.8 WDrop High
70 mm²192 A150 A25.42 V (6.35%)374.6 V41.93 V (10.48%)17609.1 WDrop High
95 mm²232 A181 A18.73 V (4.68%)381.3 V30.89 V (7.72%)12975.2 WDrop High
120 mm²269 A210 A14.83 V (3.71%)385.2 V24.46 V (6.11%)10272.0 WDrop High
150 mm²309 A241 A11.86 V (2.97%)388.1 V19.57 V (4.89%)8217.6 WDrop High
185 mm²353 A275 A9.62 V (2.4%)390.4 V15.86 V (3.97%)6662.9 WDrop High
240 mm²415 A324 A7.41 V (1.85%)392.6 V12.23 V (3.06%)5136.0 W✓ OK (≤3%)
300 mm²477 A372 A5.93 V (1.48%)394.1 V9.78 V (2.45%)4108.8 W✓ OK (≤3%)
400 mm²570 A445 A4.45 V (1.11%)395.6 V7.34 V (1.83%)3081.6 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 120 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 400A at 120 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 120m at 400V (voltage drop: 7.41V or 1.85%).

What is the power capacity of 400A at 400V?

At unity power factor, 400A at 400V supports 277.13 kW with a standard 400A circuit breaker.