450 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.28V (0.07%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.34V (0.09%)
Voltage at Load399.7 VLine Loss: 216.7 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A55.6 V (13.9%)344.4 V91.71 V (22.93%)43335.0 WDrop High
2.5 mm²24 A18 A33.36 V (8.34%)366.6 V55.03 V (13.76%)26001.0 WDrop High
4 mm²32 A25 A20.85 V (5.21%)379.2 V34.39 V (8.6%)16250.6 WDrop High
6 mm²41 A32 A13.9 V (3.47%)386.1 V22.93 V (5.73%)10833.8 WDrop High
10 mm²57 A44 A8.34 V (2.08%)391.7 V13.76 V (3.44%)6500.2 WDrop High
16 mm²76 A59 A5.21 V (1.3%)394.8 V8.6 V (2.15%)4062.7 WDrop High
25 mm²101 A78 A3.34 V (0.83%)396.7 V5.5 V (1.38%)2600.1 WDrop High
35 mm²125 A97 A2.38 V (0.6%)397.6 V3.93 V (0.98%)1857.2 WDrop High
50 mm²151 A118 A1.67 V (0.42%)398.3 V2.75 V (0.69%)1300.0 WDrop High
70 mm²192 A150 A1.19 V (0.3%)398.8 V1.97 V (0.49%)928.6 WDrop High
95 mm²232 A181 A0.88 V (0.22%)399.1 V1.45 V (0.36%)684.2 WDrop High
120 mm²269 A210 A0.69 V (0.17%)399.3 V1.15 V (0.29%)541.7 WDrop High
150 mm²309 A241 A0.56 V (0.14%)399.4 V0.92 V (0.23%)433.3 WDrop High
185 mm²353 A275 A0.45 V (0.11%)399.5 V0.74 V (0.19%)351.4 WDrop High
240 mm²415 A324 A0.35 V (0.09%)399.7 V0.57 V (0.14%)270.8 WDrop High
300 mm²477 A372 A0.28 V (0.07%)399.7 V0.46 V (0.11%)216.7 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.05%)399.8 V0.34 V (0.09%)162.5 W✓ OK (≤3%)

FAQ — 450 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 450A at 5 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 450A over 5m at 400V (voltage drop: 0.28V or 0.07%).

What is the power capacity of 450A at 400V?

At unity power factor, 450A at 400V supports 311.77 kW with a standard 450A circuit breaker.