475 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.36V (2.76%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 20.96V (9.11%)
Voltage at Load223.6 VLine Loss: 3017.8 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3388.33 V (1473.19%)0.0 V5589.17 V (2430.07%)1609458.3 WDrop High
2.5 mm²24 A18 A2033.0 V (883.91%)0.0 V3353.5 V (1458.04%)965675.0 WDrop High
4 mm²32 A25 A1270.62 V (552.45%)0.0 V2095.94 V (911.28%)603546.9 WDrop High
6 mm²41 A32 A847.08 V (368.3%)0.0 V1397.29 V (607.52%)402364.6 WDrop High
10 mm²57 A44 A508.25 V (220.98%)0.0 V838.38 V (364.51%)241418.7 WDrop High
16 mm²76 A59 A317.66 V (138.11%)0.0 V523.98 V (227.82%)150886.7 WDrop High
25 mm²101 A78 A203.3 V (88.39%)26.7 V335.35 V (145.8%)96567.5 WDrop High
35 mm²125 A97 A145.21 V (63.14%)84.8 V239.54 V (104.15%)68976.8 WDrop High
50 mm²151 A118 A101.65 V (44.2%)128.4 V167.67 V (72.9%)48283.8 WDrop High
70 mm²192 A150 A72.61 V (31.57%)157.4 V119.77 V (52.07%)34488.4 WDrop High
95 mm²232 A181 A53.5 V (23.26%)176.5 V88.25 V (38.37%)25412.5 WDrop High
120 mm²269 A210 A42.35 V (18.41%)187.6 V69.86 V (30.38%)20118.2 WDrop High
150 mm²309 A241 A33.88 V (14.73%)196.1 V55.89 V (24.3%)16094.6 WDrop High
185 mm²353 A275 A27.47 V (11.94%)202.5 V45.32 V (19.7%)13049.7 WDrop High
240 mm²415 A324 A21.18 V (9.21%)208.8 V34.93 V (15.19%)10059.1 WDrop High
300 mm²477 A372 A16.94 V (7.37%)213.1 V27.95 V (12.15%)8047.3 WDrop High
400 mm²570 A445 A12.71 V (5.52%)217.3 V20.96 V (9.11%)6035.5 WDrop High

FAQ — 475 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 475A at 250 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 475A over 250m at 230V (voltage drop: 6.36V or 2.76%).

What is the power capacity of 475A at 230V?

At unity power factor, 475A at 230V supports 109.25 kW with a standard 500A circuit breaker.