475 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.29V (0.07%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.36V (0.09%)
Voltage at Load399.7 VLine Loss: 241.4 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A58.69 V (14.67%)341.3 V96.81 V (24.2%)48283.8 WDrop High
2.5 mm²24 A18 A35.21 V (8.8%)364.8 V58.08 V (14.52%)28970.2 WDrop High
4 mm²32 A25 A22.01 V (5.5%)378.0 V36.3 V (9.08%)18106.4 WDrop High
6 mm²41 A32 A14.67 V (3.67%)385.3 V24.2 V (6.05%)12070.9 WDrop High
10 mm²57 A44 A8.8 V (2.2%)391.2 V14.52 V (3.63%)7242.6 WDrop High
16 mm²76 A59 A5.5 V (1.38%)394.5 V9.08 V (2.27%)4526.6 WDrop High
25 mm²101 A78 A3.52 V (0.88%)396.5 V5.81 V (1.45%)2897.0 WDrop High
35 mm²125 A97 A2.52 V (0.63%)397.5 V4.15 V (1.04%)2069.3 WDrop High
50 mm²151 A118 A1.76 V (0.44%)398.2 V2.9 V (0.73%)1448.5 WDrop High
70 mm²192 A150 A1.26 V (0.31%)398.7 V2.07 V (0.52%)1034.7 WDrop High
95 mm²232 A181 A0.93 V (0.23%)399.1 V1.53 V (0.38%)762.4 WDrop High
120 mm²269 A210 A0.73 V (0.18%)399.3 V1.21 V (0.3%)603.5 WDrop High
150 mm²309 A241 A0.59 V (0.15%)399.4 V0.97 V (0.24%)482.8 WDrop High
185 mm²353 A275 A0.48 V (0.12%)399.5 V0.78 V (0.2%)391.5 WDrop High
240 mm²415 A324 A0.37 V (0.09%)399.6 V0.61 V (0.15%)301.8 WDrop High
300 mm²477 A372 A0.29 V (0.07%)399.7 V0.48 V (0.12%)241.4 W✓ OK (≤3%)
400 mm²570 A445 A0.22 V (0.06%)399.8 V0.36 V (0.09%)181.1 W✓ OK (≤3%)

FAQ — 475 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 475A at 5 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 475A over 5m at 400V (voltage drop: 0.29V or 0.07%).

What is the power capacity of 475A at 400V?

At unity power factor, 475A at 400V supports 329.09 kW with a standard 500A circuit breaker.