5 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 4.32V (0.63%)
Aluminum Cable (≤3% Drop)1.5 mm²Drop: 7.13V (1.03%)
Voltage at Load685.7 VLine Loss: 37.5 W
Max Power & Breaker5.98 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.32 V (0.63%)685.7 V7.13 V (1.03%)37.5 W✓ OK (≤3%)
2.5 mm²24 A18 A2.59 V (0.38%)687.4 V4.28 V (0.62%)22.5 W✓ OK (≤3%)
4 mm²32 A25 A1.62 V (0.24%)688.4 V2.67 V (0.39%)14.0 W✓ OK (≤3%)
6 mm²41 A32 A1.08 V (0.16%)688.9 V1.78 V (0.26%)9.4 W✓ OK (≤3%)
10 mm²57 A44 A0.65 V (0.09%)689.4 V1.07 V (0.16%)5.6 W✓ OK (≤3%)
16 mm²76 A59 A0.41 V (0.06%)689.6 V0.67 V (0.1%)3.5 W✓ OK (≤3%)
25 mm²101 A78 A0.26 V (0.04%)689.7 V0.43 V (0.06%)2.2 W✓ OK (≤3%)
35 mm²125 A97 A0.19 V (0.03%)689.8 V0.31 V (0.04%)1.6 W✓ OK (≤3%)
50 mm²151 A118 A0.13 V (0.02%)689.9 V0.21 V (0.03%)1.1 W✓ OK (≤3%)
70 mm²192 A150 A0.09 V (0.01%)689.9 V0.15 V (0.02%)0.8 W✓ OK (≤3%)
95 mm²232 A181 A0.07 V (0.01%)689.9 V0.11 V (0.02%)0.6 W✓ OK (≤3%)
120 mm²269 A210 A0.05 V (0.01%)689.9 V0.09 V (0.01%)0.5 W✓ OK (≤3%)
150 mm²309 A241 A0.04 V (0.01%)690.0 V0.07 V (0.01%)0.4 W✓ OK (≤3%)
185 mm²353 A275 A0.04 V (0.01%)690.0 V0.06 V (0.01%)0.3 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.0%)690.0 V0.04 V (0.01%)0.2 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.0%)690.0 V0.04 V (0.01%)0.2 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.0%)690.0 V0.03 V (0.0%)0.1 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 5A at 35 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 5A over 35m at 690V (voltage drop: 4.32V or 0.63%).

What is the power capacity of 5A at 690V?

At unity power factor, 5A at 690V supports 5.98 kW with a standard 6A circuit breaker.