50 Amp Cable Size at 600 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 50 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 11.71V (2.93%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 9.91V (2.48%)
Voltage at Load388.3 VLine Loss: 1013.7 W
Max Power & Breaker34.64 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A741.32 V (185.33%)0.0 V1222.83 V (305.71%)64200.0 WDrop High
2.5 mm²24 A18 A444.79 V (111.2%)0.0 V733.7 V (183.42%)38520.0 WDrop High
4 mm²32 A25 A277.99 V (69.5%)122.0 V458.56 V (114.64%)24075.0 WDrop High
6 mm²41 A32 A185.33 V (46.33%)214.7 V305.71 V (76.43%)16050.0 WDrop High
10 mm²57 A44 A111.2 V (27.8%)288.8 V183.42 V (45.86%)9630.0 WDrop High
16 mm²76 A59 A69.5 V (17.37%)330.5 V114.64 V (28.66%)6018.8 WDrop High
25 mm²101 A78 A44.48 V (11.12%)355.5 V73.37 V (18.34%)3852.0 WDrop High
35 mm²125 A97 A31.77 V (7.94%)368.2 V52.41 V (13.1%)2751.4 WDrop High
50 mm²151 A118 A22.24 V (5.56%)377.8 V36.68 V (9.17%)1926.0 WDrop High
70 mm²192 A150 A15.89 V (3.97%)384.1 V26.2 V (6.55%)1375.7 W~ ≤5%
95 mm²232 A181 A11.71 V (2.93%)388.3 V19.31 V (4.83%)1013.7 W✓ OK (≤3%)
120 mm²269 A210 A9.27 V (2.32%)390.7 V15.29 V (3.82%)802.5 W✓ OK (≤3%)
150 mm²309 A241 A7.41 V (1.85%)392.6 V12.23 V (3.06%)642.0 W✓ OK (≤3%)
185 mm²353 A275 A6.01 V (1.5%)394.0 V9.91 V (2.48%)520.5 W✓ OK (≤3%)
240 mm²415 A324 A4.63 V (1.16%)395.4 V7.64 V (1.91%)401.2 W✓ OK (≤3%)
300 mm²477 A372 A3.71 V (0.93%)396.3 V6.11 V (1.53%)321.0 W✓ OK (≤3%)
400 mm²570 A445 A2.78 V (0.69%)397.2 V4.59 V (1.15%)240.7 W✓ OK (≤3%)

FAQ — 50 Amp Cable Size at 600 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 50A at 600 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 50A over 600m at 400V (voltage drop: 11.71V or 2.93%).

What is the power capacity of 50A at 400V?

At unity power factor, 50A at 400V supports 34.64 kW with a standard 50A circuit breaker.