550 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 4.9V (2.13%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 24.27V (10.55%)
Voltage at Load225.1 VLine Loss: 2697.3 W
Max Power & Breaker126.5 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3923.33 V (1705.8%)0.0 V6471.67 V (2813.77%)2157833.3 WDrop High
2.5 mm²24 A18 A2354.0 V (1023.48%)0.0 V3883.0 V (1688.26%)1294700.0 WDrop High
4 mm²32 A25 A1471.25 V (639.67%)0.0 V2426.88 V (1055.16%)809187.5 WDrop High
6 mm²41 A32 A980.83 V (426.45%)0.0 V1617.92 V (703.44%)539458.3 WDrop High
10 mm²57 A44 A588.5 V (255.87%)0.0 V970.75 V (422.07%)323675.0 WDrop High
16 mm²76 A59 A367.81 V (159.92%)0.0 V606.72 V (263.79%)202296.9 WDrop High
25 mm²101 A78 A235.4 V (102.35%)0.0 V388.3 V (168.83%)129470.0 WDrop High
35 mm²125 A97 A168.14 V (73.11%)61.9 V277.36 V (120.59%)92478.6 WDrop High
50 mm²151 A118 A117.7 V (51.17%)112.3 V194.15 V (84.41%)64735.0 WDrop High
70 mm²192 A150 A84.07 V (36.55%)145.9 V138.68 V (60.3%)46239.3 WDrop High
95 mm²232 A181 A61.95 V (26.93%)168.1 V102.18 V (44.43%)34071.1 WDrop High
120 mm²269 A210 A49.04 V (21.32%)181.0 V80.9 V (35.17%)26972.9 WDrop High
150 mm²309 A241 A39.23 V (17.06%)190.8 V64.72 V (28.14%)21578.3 WDrop High
185 mm²353 A275 A31.81 V (13.83%)198.2 V52.47 V (22.81%)17495.9 WDrop High
240 mm²415 A324 A24.52 V (10.66%)205.5 V40.45 V (17.59%)13486.5 WDrop High
300 mm²477 A372 A19.62 V (8.53%)210.4 V32.36 V (14.07%)10789.2 WDrop High
400 mm²570 A445 A14.71 V (6.4%)215.3 V24.27 V (10.55%)8091.9 WDrop High

FAQ — 550 Amp Cable Size at 250 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 550A at 250 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 550A over 250m at 230V (voltage drop: 4.9V or 2.13%).

What is the power capacity of 550A at 230V?

At unity power factor, 550A at 230V supports 126.5 kW with a standard 600A circuit breaker.