60 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 60 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 0.69V (0.17%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 0.73V (0.18%)
Voltage at Load399.3 VLine Loss: 72.2 W
Max Power & Breaker41.57 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7.41 V (1.85%)392.6 V12.23 V (3.06%)770.4 WDrop High
2.5 mm²24 A18 A4.45 V (1.11%)395.6 V7.34 V (1.83%)462.2 WDrop High
4 mm²32 A25 A2.78 V (0.69%)397.2 V4.59 V (1.15%)288.9 WDrop High
6 mm²41 A32 A1.85 V (0.46%)398.1 V3.06 V (0.76%)192.6 WDrop High
10 mm²57 A44 A1.11 V (0.28%)398.9 V1.83 V (0.46%)115.6 WDrop High
16 mm²76 A59 A0.69 V (0.17%)399.3 V1.15 V (0.29%)72.2 W✓ OK (≤3%)
25 mm²101 A78 A0.44 V (0.11%)399.6 V0.73 V (0.18%)46.2 W✓ OK (≤3%)
35 mm²125 A97 A0.32 V (0.08%)399.7 V0.52 V (0.13%)33.0 W✓ OK (≤3%)
50 mm²151 A118 A0.22 V (0.06%)399.8 V0.37 V (0.09%)23.1 W✓ OK (≤3%)
70 mm²192 A150 A0.16 V (0.04%)399.8 V0.26 V (0.07%)16.5 W✓ OK (≤3%)
95 mm²232 A181 A0.12 V (0.03%)399.9 V0.19 V (0.05%)12.2 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.02%)399.9 V0.15 V (0.04%)9.6 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.02%)399.9 V0.12 V (0.03%)7.7 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.02%)399.9 V0.1 V (0.02%)6.2 W✓ OK (≤3%)
240 mm²415 A324 A0.05 V (0.01%)400.0 V0.08 V (0.02%)4.8 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.01%)400.0 V0.06 V (0.02%)3.9 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)400.0 V0.05 V (0.01%)2.9 W✓ OK (≤3%)

FAQ — 60 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 60A at 5 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 60A over 5m at 400V (voltage drop: 0.69V or 0.17%).

What is the power capacity of 60A at 400V?

At unity power factor, 60A at 400V supports 41.57 kW with a standard 60A circuit breaker.