600 Amp Cable Size at 100 Meters (400V Three-Phase (IEC European Grid))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 100 m (328.1 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.78V (0.69%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.17V (2.29%)
Voltage at Load397.2 VLine Loss: 2889.0 W
Max Power & Breaker415.69 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 100m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1482.64 V (370.66%) | 0.0 V | 2445.66 V (611.41%) | 1540800.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 889.58 V (222.4%) | 0.0 V | 1467.39 V (366.85%) | 924480.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 555.99 V (139.0%) | 0.0 V | 917.12 V (229.28%) | 577800.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 370.66 V (92.66%) | 29.3 V | 611.41 V (152.85%) | 385200.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 222.4 V (55.6%) | 177.6 V | 366.85 V (91.71%) | 231120.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 139.0 V (34.75%) | 261.0 V | 229.28 V (57.32%) | 144450.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 88.96 V (22.24%) | 311.0 V | 146.74 V (36.68%) | 92448.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 63.54 V (15.89%) | 336.5 V | 104.81 V (26.2%) | 66034.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 44.48 V (11.12%) | 355.5 V | 73.37 V (18.34%) | 46224.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 31.77 V (7.94%) | 368.2 V | 52.41 V (13.1%) | 33017.1 W | Drop High |
| 95 mm² | 232 A | 181 A | 23.41 V (5.85%) | 376.6 V | 38.62 V (9.65%) | 24328.4 W | Drop High |
| 120 mm² | 269 A | 210 A | 18.53 V (4.63%) | 381.5 V | 30.57 V (7.64%) | 19260.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 14.83 V (3.71%) | 385.2 V | 24.46 V (6.11%) | 15408.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 12.02 V (3.01%) | 388.0 V | 19.83 V (4.96%) | 12493.0 W | Drop High |
| 240 mm² | 415 A | 324 A | 9.27 V (2.32%) | 390.7 V | 15.29 V (3.82%) | 9630.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 7.41 V (1.85%) | 392.6 V | 12.23 V (3.06%) | 7704.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 5.56 V (1.39%) | 394.4 V | 9.17 V (2.29%) | 5778.0 W | Drop High |
FAQ — 600 Amp Cable Size at 100 Meters (400V Three-Phase (IEC European Grid))
What mm² cable size is required for 600A at 100 meters (400V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 600A over 100m at 400V (voltage drop: 2.78V or 0.69%).
What is the power capacity of 600A at 400V?
At unity power factor, 600A at 400V supports 415.69 kW with a standard 600A circuit breaker.
Related Lengths & Currents (400V)
600A · 5m (400V)600A · 10m (400V)600A · 15m (400V)600A · 20m (400V)600A · 25m (400V)600A · 30m (400V)600A · 35m (400V)600A · 40m (400V)600A · 45m (400V)600A · 50m (400V)600A · 60m (400V)600A · 70m (400V)10A · 100m (400V)16A · 100m (400V)20A · 100m (400V)25A · 100m (400V)32A · 100m (400V)40A · 100m (400V)50A · 100m (400V)63A · 100m (400V)80A · 100m (400V)100A · 100m (400V)125A · 100m (400V)160A · 100m (400V)200A · 100m (400V)