600 Amp Cable Size at 200 Meters (400V Three-Phase (IEC European Grid))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 200 m (656.2 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.56V (1.39%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 18.34V (4.59%)
Voltage at Load394.4 VLine Loss: 5778.0 W
Max Power & Breaker415.69 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 200m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2965.27 V (741.32%) | 0.0 V | 4891.31 V (1222.83%) | 3081600.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1779.16 V (444.79%) | 0.0 V | 2934.79 V (733.7%) | 1848960.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1111.98 V (277.99%) | 0.0 V | 1834.24 V (458.56%) | 1155600.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 741.32 V (185.33%) | 0.0 V | 1222.83 V (305.71%) | 770400.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 444.79 V (111.2%) | 0.0 V | 733.7 V (183.42%) | 462240.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 277.99 V (69.5%) | 122.0 V | 458.56 V (114.64%) | 288900.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 177.92 V (44.48%) | 222.1 V | 293.48 V (73.37%) | 184896.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 127.08 V (31.77%) | 272.9 V | 209.63 V (52.41%) | 132068.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 88.96 V (22.24%) | 311.0 V | 146.74 V (36.68%) | 92448.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 63.54 V (15.89%) | 336.5 V | 104.81 V (26.2%) | 66034.3 W | Drop High |
| 95 mm² | 232 A | 181 A | 46.82 V (11.71%) | 353.2 V | 77.23 V (19.31%) | 48656.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 37.07 V (9.27%) | 362.9 V | 61.14 V (15.29%) | 38520.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 29.65 V (7.41%) | 370.3 V | 48.91 V (12.23%) | 30816.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 24.04 V (6.01%) | 376.0 V | 39.66 V (9.91%) | 24985.9 W | Drop High |
| 240 mm² | 415 A | 324 A | 18.53 V (4.63%) | 381.5 V | 30.57 V (7.64%) | 19260.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 14.83 V (3.71%) | 385.2 V | 24.46 V (6.11%) | 15408.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 11.12 V (2.78%) | 388.9 V | 18.34 V (4.59%) | 11556.0 W | Drop High |
FAQ — 600 Amp Cable Size at 200 Meters (400V Three-Phase (IEC European Grid))
What mm² cable size is required for 600A at 200 meters (400V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 600A over 200m at 400V (voltage drop: 5.56V or 1.39%).
What is the power capacity of 600A at 400V?
At unity power factor, 600A at 400V supports 415.69 kW with a standard 600A circuit breaker.
Related Lengths & Currents (400V)
600A · 5m (400V)600A · 10m (400V)600A · 15m (400V)600A · 20m (400V)600A · 25m (400V)600A · 30m (400V)600A · 35m (400V)600A · 40m (400V)600A · 45m (400V)600A · 50m (400V)600A · 60m (400V)600A · 70m (400V)10A · 200m (400V)16A · 200m (400V)20A · 200m (400V)25A · 200m (400V)32A · 200m (400V)40A · 200m (400V)50A · 200m (400V)63A · 200m (400V)80A · 200m (400V)100A · 200m (400V)125A · 200m (400V)160A · 200m (400V)200A · 200m (400V)