63 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 63 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 17.51V (2.54%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 18.49V (2.68%)
Voltage at Load672.5 VLine Loss: 1911.1 W
Max Power & Breaker75.29 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A186.81 V (27.07%)503.2 V308.15 V (44.66%)20384.8 WDrop High
2.5 mm²24 A18 A112.09 V (16.24%)577.9 V184.89 V (26.8%)12230.9 WDrop High
4 mm²32 A25 A70.05 V (10.15%)619.9 V115.56 V (16.75%)7644.3 WDrop High
6 mm²41 A32 A46.7 V (6.77%)643.3 V77.04 V (11.16%)5096.2 WDrop High
10 mm²57 A44 A28.02 V (4.06%)662.0 V46.22 V (6.7%)3057.7 WDrop High
16 mm²76 A59 A17.51 V (2.54%)672.5 V28.89 V (4.19%)1911.1 W✓ OK (≤3%)
25 mm²101 A78 A11.21 V (1.62%)678.8 V18.49 V (2.68%)1223.1 W✓ OK (≤3%)
35 mm²125 A97 A8.01 V (1.16%)682.0 V13.21 V (1.91%)873.6 W✓ OK (≤3%)
50 mm²151 A118 A5.6 V (0.81%)684.4 V9.24 V (1.34%)611.5 W✓ OK (≤3%)
70 mm²192 A150 A4.0 V (0.58%)686.0 V6.6 V (0.96%)436.8 W✓ OK (≤3%)
95 mm²232 A181 A2.95 V (0.43%)687.1 V4.87 V (0.71%)321.9 W✓ OK (≤3%)
120 mm²269 A210 A2.34 V (0.34%)687.7 V3.85 V (0.56%)254.8 W✓ OK (≤3%)
150 mm²309 A241 A1.87 V (0.27%)688.1 V3.08 V (0.45%)203.8 W✓ OK (≤3%)
185 mm²353 A275 A1.51 V (0.22%)688.5 V2.5 V (0.36%)165.3 W✓ OK (≤3%)
240 mm²415 A324 A1.17 V (0.17%)688.8 V1.93 V (0.28%)127.4 W✓ OK (≤3%)
300 mm²477 A372 A0.93 V (0.14%)689.1 V1.54 V (0.22%)101.9 W✓ OK (≤3%)
400 mm²570 A445 A0.7 V (0.1%)689.3 V1.16 V (0.17%)76.4 W✓ OK (≤3%)

FAQ — 63 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 63A at 120 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 63A over 120m at 690V (voltage drop: 17.51V or 2.54%).

What is the power capacity of 63A at 690V?

At unity power factor, 63A at 690V supports 75.29 kW with a standard 63A circuit breaker.