700 Amp Cable Size at 25 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.81V (0.2%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.67V (0.67%)
Voltage at Load399.2 VLine Loss: 983.0 W
Max Power & Breaker484.97 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A432.44 V (108.11%)0.0 V713.32 V (178.33%)524300.0 WDrop High
2.5 mm²24 A18 A259.46 V (64.87%)140.5 V427.99 V (107.0%)314580.0 WDrop High
4 mm²32 A25 A162.16 V (40.54%)237.8 V267.49 V (66.87%)196612.5 WDrop High
6 mm²41 A32 A108.11 V (27.03%)291.9 V178.33 V (44.58%)131075.0 WDrop High
10 mm²57 A44 A64.87 V (16.22%)335.1 V107.0 V (26.75%)78645.0 WDrop High
16 mm²76 A59 A40.54 V (10.14%)359.5 V66.87 V (16.72%)49153.1 WDrop High
25 mm²101 A78 A25.95 V (6.49%)374.1 V42.8 V (10.7%)31458.0 WDrop High
35 mm²125 A97 A18.53 V (4.63%)381.5 V30.57 V (7.64%)22470.0 WDrop High
50 mm²151 A118 A12.97 V (3.24%)387.0 V21.4 V (5.35%)15729.0 WDrop High
70 mm²192 A150 A9.27 V (2.32%)390.7 V15.29 V (3.82%)11235.0 WDrop High
95 mm²232 A181 A6.83 V (1.71%)393.2 V11.26 V (2.82%)8278.4 WDrop High
120 mm²269 A210 A5.41 V (1.35%)394.6 V8.92 V (2.23%)6553.7 WDrop High
150 mm²309 A241 A4.32 V (1.08%)395.7 V7.13 V (1.78%)5243.0 WDrop High
185 mm²353 A275 A3.51 V (0.88%)396.5 V5.78 V (1.45%)4251.1 WDrop High
240 mm²415 A324 A2.7 V (0.68%)397.3 V4.46 V (1.11%)3276.9 WDrop High
300 mm²477 A372 A2.16 V (0.54%)397.8 V3.57 V (0.89%)2621.5 WDrop High
400 mm²570 A445 A1.62 V (0.41%)398.4 V2.67 V (0.67%)1966.1 WDrop High

FAQ — 700 Amp Cable Size at 25 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 700A at 25 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 25m at 400V (voltage drop: 0.81V or 0.2%).

What is the power capacity of 700A at 400V?

At unity power factor, 700A at 400V supports 484.97 kW with a standard 700A circuit breaker.