80 Amp Cable Size at 90 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 10.67V (2.67%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 8.8V (2.2%)
Voltage at Load389.3 VLine Loss: 1479.2 W
Max Power & Breaker55.43 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A177.92 V (44.48%)222.1 V293.48 V (73.37%)24652.8 WDrop High
2.5 mm²24 A18 A106.75 V (26.69%)293.3 V176.09 V (44.02%)14791.7 WDrop High
4 mm²32 A25 A66.72 V (16.68%)333.3 V110.05 V (27.51%)9244.8 WDrop High
6 mm²41 A32 A44.48 V (11.12%)355.5 V73.37 V (18.34%)6163.2 WDrop High
10 mm²57 A44 A26.69 V (6.67%)373.3 V44.02 V (11.01%)3697.9 WDrop High
16 mm²76 A59 A16.68 V (4.17%)383.3 V27.51 V (6.88%)2311.2 WDrop High
25 mm²101 A78 A10.67 V (2.67%)389.3 V17.61 V (4.4%)1479.2 W✓ OK (≤3%)
35 mm²125 A97 A7.62 V (1.91%)392.4 V12.58 V (3.14%)1056.5 W✓ OK (≤3%)
50 mm²151 A118 A5.34 V (1.33%)394.7 V8.8 V (2.2%)739.6 W✓ OK (≤3%)
70 mm²192 A150 A3.81 V (0.95%)396.2 V6.29 V (1.57%)528.3 W✓ OK (≤3%)
95 mm²232 A181 A2.81 V (0.7%)397.2 V4.63 V (1.16%)389.3 W✓ OK (≤3%)
120 mm²269 A210 A2.22 V (0.56%)397.8 V3.67 V (0.92%)308.2 W✓ OK (≤3%)
150 mm²309 A241 A1.78 V (0.44%)398.2 V2.93 V (0.73%)246.5 W✓ OK (≤3%)
185 mm²353 A275 A1.44 V (0.36%)398.6 V2.38 V (0.59%)199.9 W✓ OK (≤3%)
240 mm²415 A324 A1.11 V (0.28%)398.9 V1.83 V (0.46%)154.1 W✓ OK (≤3%)
300 mm²477 A372 A0.89 V (0.22%)399.1 V1.47 V (0.37%)123.3 W✓ OK (≤3%)
400 mm²570 A445 A0.67 V (0.17%)399.3 V1.1 V (0.28%)92.4 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 90 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 80A at 90 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 80A over 90m at 400V (voltage drop: 10.67V or 2.67%).

What is the power capacity of 80A at 400V?

At unity power factor, 80A at 400V supports 55.43 kW with a standard 80A circuit breaker.