800 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.29V (0.19%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.28V (0.62%)
Voltage at Load688.7 VLine Loss: 1797.6 W
Max Power & Breaker956.09 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A691.9 V (100.27%)0.0 V1141.31 V (165.41%)958720.0 WDrop High
2.5 mm²24 A18 A415.14 V (60.16%)274.9 V684.78 V (99.24%)575232.0 WDrop High
4 mm²32 A25 A259.46 V (37.6%)430.5 V427.99 V (62.03%)359520.0 WDrop High
6 mm²41 A32 A172.97 V (25.07%)517.0 V285.33 V (41.35%)239680.0 WDrop High
10 mm²57 A44 A103.78 V (15.04%)586.2 V171.2 V (24.81%)143808.0 WDrop High
16 mm²76 A59 A64.87 V (9.4%)625.1 V107.0 V (15.51%)89880.0 WDrop High
25 mm²101 A78 A41.51 V (6.02%)648.5 V68.48 V (9.92%)57523.2 WDrop High
35 mm²125 A97 A29.65 V (4.3%)660.3 V48.91 V (7.09%)41088.0 WDrop High
50 mm²151 A118 A20.76 V (3.01%)669.2 V34.24 V (4.96%)28761.6 WDrop High
70 mm²192 A150 A14.83 V (2.15%)675.2 V24.46 V (3.54%)20544.0 WDrop High
95 mm²232 A181 A10.92 V (1.58%)679.1 V18.02 V (2.61%)15137.7 WDrop High
120 mm²269 A210 A8.65 V (1.25%)681.4 V14.27 V (2.07%)11984.0 WDrop High
150 mm²309 A241 A6.92 V (1.0%)683.1 V11.41 V (1.65%)9587.2 WDrop High
185 mm²353 A275 A5.61 V (0.81%)684.4 V9.25 V (1.34%)7773.4 WDrop High
240 mm²415 A324 A4.32 V (0.63%)685.7 V7.13 V (1.03%)5992.0 WDrop High
300 mm²477 A372 A3.46 V (0.5%)686.5 V5.71 V (0.83%)4793.6 WDrop High
400 mm²570 A445 A2.59 V (0.38%)687.4 V4.28 V (0.62%)3595.2 WDrop High

FAQ — 800 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 800A at 35 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 35m at 690V (voltage drop: 1.29V or 0.19%).

What is the power capacity of 800A at 690V?

At unity power factor, 800A at 690V supports 956.09 kW with a standard 800A circuit breaker.