800 Amp Cable Size at 70 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.0V (1.3%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.88V (4.3%)
Voltage at Load227.0 VLine Loss: 2396.8 W
Max Power & Breaker184.0 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1597.87 V (694.72%)0.0 V2635.73 V (1145.97%)1278293.3 WDrop High
2.5 mm²24 A18 A958.72 V (416.83%)0.0 V1581.44 V (687.58%)766976.0 WDrop High
4 mm²32 A25 A599.2 V (260.52%)0.0 V988.4 V (429.74%)479360.0 WDrop High
6 mm²41 A32 A399.47 V (173.68%)0.0 V658.93 V (286.49%)319573.3 WDrop High
10 mm²57 A44 A239.68 V (104.21%)0.0 V395.36 V (171.9%)191744.0 WDrop High
16 mm²76 A59 A149.8 V (65.13%)80.2 V247.1 V (107.43%)119840.0 WDrop High
25 mm²101 A78 A95.87 V (41.68%)134.1 V158.14 V (68.76%)76697.6 WDrop High
35 mm²125 A97 A68.48 V (29.77%)161.5 V112.96 V (49.11%)54784.0 WDrop High
50 mm²151 A118 A47.94 V (20.84%)182.1 V79.07 V (34.38%)38348.8 WDrop High
70 mm²192 A150 A34.24 V (14.89%)195.8 V56.48 V (24.56%)27392.0 WDrop High
95 mm²232 A181 A25.23 V (10.97%)204.8 V41.62 V (18.09%)20183.6 WDrop High
120 mm²269 A210 A19.97 V (8.68%)210.0 V32.95 V (14.32%)15978.7 WDrop High
150 mm²309 A241 A15.98 V (6.95%)214.0 V26.36 V (11.46%)12782.9 WDrop High
185 mm²353 A275 A12.96 V (5.63%)217.0 V21.37 V (9.29%)10364.5 WDrop High
240 mm²415 A324 A9.99 V (4.34%)220.0 V16.47 V (7.16%)7989.3 WDrop High
300 mm²477 A372 A7.99 V (3.47%)222.0 V13.18 V (5.73%)6391.5 WDrop High
400 mm²570 A445 A5.99 V (2.61%)224.0 V9.88 V (4.3%)4793.6 WDrop High

FAQ — 800 Amp Cable Size at 70 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 800A at 70 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 70m at 230V (voltage drop: 3.0V or 1.3%).

What is the power capacity of 800A at 230V?

At unity power factor, 800A at 230V supports 184.0 kW with a standard 800A circuit breaker.