90 Amp Cable Size at 20 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 90 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 3.08V (1.34%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 3.63V (1.58%)
Voltage at Load226.9 VLine Loss: 277.3 W
Max Power & Breaker20.7 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A51.36 V (22.33%)178.6 V84.72 V (36.83%)4622.4 WDrop High
2.5 mm²24 A18 A30.82 V (13.4%)199.2 V50.83 V (22.1%)2773.4 WDrop High
4 mm²32 A25 A19.26 V (8.37%)210.7 V31.77 V (13.81%)1733.4 WDrop High
6 mm²41 A32 A12.84 V (5.58%)217.2 V21.18 V (9.21%)1155.6 WDrop High
10 mm²57 A44 A7.7 V (3.35%)222.3 V12.71 V (5.53%)693.4 WDrop High
16 mm²76 A59 A4.81 V (2.09%)225.2 V7.94 V (3.45%)433.3 WDrop High
25 mm²101 A78 A3.08 V (1.34%)226.9 V5.08 V (2.21%)277.3 W✓ OK (≤3%)
35 mm²125 A97 A2.2 V (0.96%)227.8 V3.63 V (1.58%)198.1 W✓ OK (≤3%)
50 mm²151 A118 A1.54 V (0.67%)228.5 V2.54 V (1.11%)138.7 W✓ OK (≤3%)
70 mm²192 A150 A1.1 V (0.48%)228.9 V1.82 V (0.79%)99.1 W✓ OK (≤3%)
95 mm²232 A181 A0.81 V (0.35%)229.2 V1.34 V (0.58%)73.0 W✓ OK (≤3%)
120 mm²269 A210 A0.64 V (0.28%)229.4 V1.06 V (0.46%)57.8 W✓ OK (≤3%)
150 mm²309 A241 A0.51 V (0.22%)229.5 V0.85 V (0.37%)46.2 W✓ OK (≤3%)
185 mm²353 A275 A0.42 V (0.18%)229.6 V0.69 V (0.3%)37.5 W✓ OK (≤3%)
240 mm²415 A324 A0.32 V (0.14%)229.7 V0.53 V (0.23%)28.9 W✓ OK (≤3%)
300 mm²477 A372 A0.26 V (0.11%)229.7 V0.42 V (0.18%)23.1 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.08%)229.8 V0.32 V (0.14%)17.3 W✓ OK (≤3%)

FAQ — 90 Amp Cable Size at 20 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 90A at 20 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 90A over 20m at 230V (voltage drop: 3.08V or 1.34%).

What is the power capacity of 90A at 230V?

At unity power factor, 90A at 230V supports 20.7 kW with a standard 90A circuit breaker.