Kabeltværsnit for 1000 Ampere ved 250 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 1000 A over 250 m ved 230V.
Copper Cable (≤3% Drop)4× 400 mm²Drop: 6.69V (2.91%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 44.12V (19.18%)
Voltage at Load223.3 VLine Loss: 6687.5 W
Max Power & Breaker230.0 kW1000A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 250m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 7133.33 V (3101.45%) | 0.0 V | 11766.67 V (5115.94%) | 7133333.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 4280.0 V (1860.87%) | 0.0 V | 7060.0 V (3069.57%) | 4280000.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 2675.0 V (1163.04%) | 0.0 V | 4412.5 V (1918.48%) | 2675000.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 1783.33 V (775.36%) | 0.0 V | 2941.67 V (1278.99%) | 1783333.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 1070.0 V (465.22%) | 0.0 V | 1765.0 V (767.39%) | 1070000.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 668.75 V (290.76%) | 0.0 V | 1103.12 V (479.62%) | 668750.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 428.0 V (186.09%) | 0.0 V | 706.0 V (306.96%) | 428000.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 305.71 V (132.92%) | 0.0 V | 504.29 V (219.25%) | 305714.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 214.0 V (93.04%) | 16.0 V | 353.0 V (153.48%) | 214000.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 152.86 V (66.46%) | 77.1 V | 252.14 V (109.63%) | 152857.1 W | Drop High |
| 95 mm² | 232 A | 181 A | 112.63 V (48.97%) | 117.4 V | 185.79 V (80.78%) | 112631.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 89.17 V (38.77%) | 140.8 V | 147.08 V (63.95%) | 89166.7 W | Drop High |
| 150 mm² | 309 A | 241 A | 71.33 V (31.01%) | 158.7 V | 117.67 V (51.16%) | 71333.3 W | Drop High |
| 185 mm² | 353 A | 275 A | 57.84 V (25.15%) | 172.2 V | 95.41 V (41.48%) | 57837.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 44.58 V (19.38%) | 185.4 V | 73.54 V (31.97%) | 44583.3 W | Drop High |
| 300 mm² | 477 A | 372 A | 35.67 V (15.51%) | 194.3 V | 58.83 V (25.58%) | 35666.7 W | Drop High |
| 400 mm² | 570 A | 445 A | 26.75 V (11.63%) | 203.2 V | 44.12 V (19.18%) | 26750.0 W | Drop High |
FAQ — Kabeltværsnit for 1000 Ampere ved 250 Meter (230V)
Hvilket kabeltværsnit kræves til 1000A ved 250 meter (230V)?
Til 1000 Ampere over 250 meter ved 230V anbefales 4× 400 mm² kobberkabel (spændingsfald 6.69V / 2.91%).
Hvor mange kW svarer 1000A ved 230V til?
Det svarer til 230.0 kW med en anbefalet sikring på 1000A.
Related Lengths & Currents (230V)
1000A · 5m (230V)1000A · 10m (230V)1000A · 15m (230V)1000A · 20m (230V)1000A · 25m (230V)1000A · 30m (230V)1000A · 35m (230V)1000A · 40m (230V)1000A · 45m (230V)1000A · 50m (230V)1000A · 60m (230V)1000A · 70m (230V)10A · 250m (230V)16A · 250m (230V)20A · 250m (230V)25A · 250m (230V)32A · 250m (230V)40A · 250m (230V)50A · 250m (230V)63A · 250m (230V)80A · 250m (230V)100A · 250m (230V)125A · 250m (230V)160A · 250m (230V)200A · 250m (230V)