Kabeltværsnit for 275 Ampere ved 60 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 275 A over 60 m ved 230V.

Copper Cable (≤3% Drop)150 mm²Drop: 4.71V (2.05%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 6.3V (2.74%)
Voltage at Load225.3 VLine Loss: 1294.7 W
Max Power & Breaker63.25 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A470.8 V (204.7%)0.0 V776.6 V (337.65%)129470.0 WDrop High
2.5 mm²24 A18 A282.48 V (122.82%)0.0 V465.96 V (202.59%)77682.0 WDrop High
4 mm²32 A25 A176.55 V (76.76%)53.4 V291.22 V (126.62%)48551.2 WDrop High
6 mm²41 A32 A117.7 V (51.17%)112.3 V194.15 V (84.41%)32367.5 WDrop High
10 mm²57 A44 A70.62 V (30.7%)159.4 V116.49 V (50.65%)19420.5 WDrop High
16 mm²76 A59 A44.14 V (19.19%)185.9 V72.81 V (31.65%)12137.8 WDrop High
25 mm²101 A78 A28.25 V (12.28%)201.8 V46.6 V (20.26%)7768.2 WDrop High
35 mm²125 A97 A20.18 V (8.77%)209.8 V33.28 V (14.47%)5548.7 WDrop High
50 mm²151 A118 A14.12 V (6.14%)215.9 V23.3 V (10.13%)3884.1 WDrop High
70 mm²192 A150 A10.09 V (4.39%)219.9 V16.64 V (7.24%)2774.4 WDrop High
95 mm²232 A181 A7.43 V (3.23%)222.6 V12.26 V (5.33%)2044.3 WDrop High
120 mm²269 A210 A5.88 V (2.56%)224.1 V9.71 V (4.22%)1618.4 WDrop High
150 mm²309 A241 A4.71 V (2.05%)225.3 V7.77 V (3.38%)1294.7 W✓ OK (≤3%)
185 mm²353 A275 A3.82 V (1.66%)226.2 V6.3 V (2.74%)1049.8 W✓ OK (≤3%)
240 mm²415 A324 A2.94 V (1.28%)227.1 V4.85 V (2.11%)809.2 W✓ OK (≤3%)
300 mm²477 A372 A2.35 V (1.02%)227.6 V3.88 V (1.69%)647.4 W✓ OK (≤3%)
400 mm²570 A445 A1.77 V (0.77%)228.2 V2.91 V (1.27%)485.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 275 Ampere ved 60 Meter (230V)

Hvilket kabeltværsnit kræves til 275A ved 60 meter (230V)?

Til 275 Ampere over 60 meter ved 230V anbefales 150 mm² kobberkabel (spændingsfald 4.71V / 2.05%).

Hvor mange kW svarer 275A ved 230V til?

Det svarer til 63.25 kW med en anbefalet sikring på 300A.