Kabeltværsnit for 30 Ampere ved 350 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 30 A over 350 m ved 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 6.18V (2.69%)
Voltage at Load223.6 VLine Loss: 192.6 W
Max Power & Breaker6.9 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A299.6 V (130.26%)0.0 V494.2 V (214.87%)8988.0 WDrop High
2.5 mm²24 A18 A179.76 V (78.16%)50.2 V296.52 V (128.92%)5392.8 WDrop High
4 mm²32 A25 A112.35 V (48.85%)117.7 V185.32 V (80.58%)3370.5 WDrop High
6 mm²41 A32 A74.9 V (32.57%)155.1 V123.55 V (53.72%)2247.0 WDrop High
10 mm²57 A44 A44.94 V (19.54%)185.1 V74.13 V (32.23%)1348.2 WDrop High
16 mm²76 A59 A28.09 V (12.21%)201.9 V46.33 V (20.14%)842.6 WDrop High
25 mm²101 A78 A17.98 V (7.82%)212.0 V29.65 V (12.89%)539.3 WDrop High
35 mm²125 A97 A12.84 V (5.58%)217.2 V21.18 V (9.21%)385.2 WDrop High
50 mm²151 A118 A8.99 V (3.91%)221.0 V14.83 V (6.45%)269.6 W~ ≤5%
70 mm²192 A150 A6.42 V (2.79%)223.6 V10.59 V (4.6%)192.6 W✓ OK (≤3%)
95 mm²232 A181 A4.73 V (2.06%)225.3 V7.8 V (3.39%)141.9 W✓ OK (≤3%)
120 mm²269 A210 A3.74 V (1.63%)226.3 V6.18 V (2.69%)112.3 W✓ OK (≤3%)
150 mm²309 A241 A3.0 V (1.3%)227.0 V4.94 V (2.15%)89.9 W✓ OK (≤3%)
185 mm²353 A275 A2.43 V (1.06%)227.6 V4.01 V (1.74%)72.9 W✓ OK (≤3%)
240 mm²415 A324 A1.87 V (0.81%)228.1 V3.09 V (1.34%)56.2 W✓ OK (≤3%)
300 mm²477 A372 A1.5 V (0.65%)228.5 V2.47 V (1.07%)44.9 W✓ OK (≤3%)
400 mm²570 A445 A1.12 V (0.49%)228.9 V1.85 V (0.81%)33.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 30 Ampere ved 350 Meter (230V)

Hvilket kabeltværsnit kræves til 30A ved 350 meter (230V)?

Til 30 Ampere over 350 meter ved 230V anbefales 70 mm² kobberkabel (spændingsfald 6.42V / 2.79%).

Hvor mange kW svarer 30A ved 230V til?

Det svarer til 6.9 kW med en anbefalet sikring på 30A.