Kabeltværsnit for 300 Ampere ved 70 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 300 A over 70 m ved 230V.

Copper Cable (≤3% Drop)150 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 6.18V (2.69%)
Voltage at Load224.0 VLine Loss: 1797.6 W
Max Power & Breaker69.0 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A599.2 V (260.52%)0.0 V988.4 V (429.74%)179760.0 WDrop High
2.5 mm²24 A18 A359.52 V (156.31%)0.0 V593.04 V (257.84%)107856.0 WDrop High
4 mm²32 A25 A224.7 V (97.7%)5.3 V370.65 V (161.15%)67410.0 WDrop High
6 mm²41 A32 A149.8 V (65.13%)80.2 V247.1 V (107.43%)44940.0 WDrop High
10 mm²57 A44 A89.88 V (39.08%)140.1 V148.26 V (64.46%)26964.0 WDrop High
16 mm²76 A59 A56.17 V (24.42%)173.8 V92.66 V (40.29%)16852.5 WDrop High
25 mm²101 A78 A35.95 V (15.63%)194.0 V59.3 V (25.78%)10785.6 WDrop High
35 mm²125 A97 A25.68 V (11.17%)204.3 V42.36 V (18.42%)7704.0 WDrop High
50 mm²151 A118 A17.98 V (7.82%)212.0 V29.65 V (12.89%)5392.8 WDrop High
70 mm²192 A150 A12.84 V (5.58%)217.2 V21.18 V (9.21%)3852.0 WDrop High
95 mm²232 A181 A9.46 V (4.11%)220.5 V15.61 V (6.79%)2838.3 WDrop High
120 mm²269 A210 A7.49 V (3.26%)222.5 V12.36 V (5.37%)2247.0 WDrop High
150 mm²309 A241 A5.99 V (2.61%)224.0 V9.88 V (4.3%)1797.6 W✓ OK (≤3%)
185 mm²353 A275 A4.86 V (2.11%)225.1 V8.01 V (3.48%)1457.5 W✓ OK (≤3%)
240 mm²415 A324 A3.75 V (1.63%)226.3 V6.18 V (2.69%)1123.5 W✓ OK (≤3%)
300 mm²477 A372 A3.0 V (1.3%)227.0 V4.94 V (2.15%)898.8 W✓ OK (≤3%)
400 mm²570 A445 A2.25 V (0.98%)227.8 V3.71 V (1.61%)674.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 300 Ampere ved 70 Meter (230V)

Hvilket kabeltværsnit kræves til 300A ved 70 meter (230V)?

Til 300 Ampere over 70 meter ved 230V anbefales 150 mm² kobberkabel (spændingsfald 5.99V / 2.61%).

Hvor mange kW svarer 300A ved 230V til?

Det svarer til 69.0 kW med en anbefalet sikring på 300A.