Kabeltværsnit for 325 Ampere ved 120 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 325 A over 120 m ved 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 7.81V (1.95%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 7.95V (1.99%)
Voltage at Load392.2 VLine Loss: 4398.6 W
Max Power & Breaker225.17 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A963.71 V (240.93%)0.0 V1589.68 V (397.42%)542490.0 WDrop High
2.5 mm²24 A18 A578.23 V (144.56%)0.0 V953.81 V (238.45%)325494.0 WDrop High
4 mm²32 A25 A361.39 V (90.35%)38.6 V596.13 V (149.03%)203433.8 WDrop High
6 mm²41 A32 A240.93 V (60.23%)159.1 V397.42 V (99.35%)135622.5 WDrop High
10 mm²57 A44 A144.56 V (36.14%)255.4 V238.45 V (59.61%)81373.5 WDrop High
16 mm²76 A59 A90.35 V (22.59%)309.7 V149.03 V (37.26%)50858.4 WDrop High
25 mm²101 A78 A57.82 V (14.46%)342.2 V95.38 V (23.85%)32549.4 WDrop High
35 mm²125 A97 A41.3 V (10.33%)358.7 V68.13 V (17.03%)23249.6 WDrop High
50 mm²151 A118 A28.91 V (7.23%)371.1 V47.69 V (11.92%)16274.7 WDrop High
70 mm²192 A150 A20.65 V (5.16%)379.3 V34.06 V (8.52%)11624.8 WDrop High
95 mm²232 A181 A15.22 V (3.8%)384.8 V25.1 V (6.28%)8565.6 WDrop High
120 mm²269 A210 A12.05 V (3.01%)388.0 V19.87 V (4.97%)6781.1 WDrop High
150 mm²309 A241 A9.64 V (2.41%)390.4 V15.9 V (3.97%)5424.9 WDrop High
185 mm²353 A275 A7.81 V (1.95%)392.2 V12.89 V (3.22%)4398.6 W✓ OK (≤3%)
240 mm²415 A324 A6.02 V (1.51%)394.0 V9.94 V (2.48%)3390.6 W✓ OK (≤3%)
300 mm²477 A372 A4.82 V (1.2%)395.2 V7.95 V (1.99%)2712.4 W✓ OK (≤3%)
400 mm²570 A445 A3.61 V (0.9%)396.4 V5.96 V (1.49%)2034.3 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 325 Ampere ved 120 Meter (400V)

Hvilket kabeltværsnit kræves til 325A ved 120 meter (400V)?

Til 325 Ampere over 120 meter ved 400V anbefales 185 mm² kobberkabel (spændingsfald 7.81V / 1.95%).

Hvor mange kW svarer 325A ved 400V til?

Det svarer til 225.17 kW med en anbefalet sikring på 350A.