Kabeltværsnit for 325 Ampere ved 150 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 325 A over 150 m ved 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 5.22V (2.27%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.6V (3.74%)
Voltage at Load224.8 VLine Loss: 1695.3 W
Max Power & Breaker74.75 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1391.0 V (604.78%)0.0 V2294.5 V (997.61%)452075.0 WDrop High
2.5 mm²24 A18 A834.6 V (362.87%)0.0 V1376.7 V (598.57%)271245.0 WDrop High
4 mm²32 A25 A521.62 V (226.79%)0.0 V860.44 V (374.1%)169528.1 WDrop High
6 mm²41 A32 A347.75 V (151.2%)0.0 V573.62 V (249.4%)113018.8 WDrop High
10 mm²57 A44 A208.65 V (90.72%)21.3 V344.17 V (149.64%)67811.2 WDrop High
16 mm²76 A59 A130.41 V (56.7%)99.6 V215.11 V (93.53%)42382.0 WDrop High
25 mm²101 A78 A83.46 V (36.29%)146.5 V137.67 V (59.86%)27124.5 WDrop High
35 mm²125 A97 A59.61 V (25.92%)170.4 V98.34 V (42.75%)19374.6 WDrop High
50 mm²151 A118 A41.73 V (18.14%)188.3 V68.83 V (29.93%)13562.2 WDrop High
70 mm²192 A150 A29.81 V (12.96%)200.2 V49.17 V (21.38%)9687.3 WDrop High
95 mm²232 A181 A21.96 V (9.55%)208.0 V36.23 V (15.75%)7138.0 WDrop High
120 mm²269 A210 A17.39 V (7.56%)212.6 V28.68 V (12.47%)5650.9 WDrop High
150 mm²309 A241 A13.91 V (6.05%)216.1 V22.95 V (9.98%)4520.8 WDrop High
185 mm²353 A275 A11.28 V (4.9%)218.7 V18.6 V (8.09%)3665.5 W~ ≤5%
240 mm²415 A324 A8.69 V (3.78%)221.3 V14.34 V (6.24%)2825.5 W~ ≤5%
300 mm²477 A372 A6.96 V (3.02%)223.0 V11.47 V (4.99%)2260.4 W~ ≤5%
400 mm²570 A445 A5.22 V (2.27%)224.8 V8.6 V (3.74%)1695.3 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 325 Ampere ved 150 Meter (230V)

Hvilket kabeltværsnit kræves til 325A ved 150 meter (230V)?

Til 325 Ampere over 150 meter ved 230V anbefales 400 mm² kobberkabel (spændingsfald 5.22V / 2.27%).

Hvor mange kW svarer 325A ved 230V til?

Det svarer til 74.75 kW med en anbefalet sikring på 350A.