Kabeltværsnit for 325 Ampere ved 350 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 325 A over 350 m ved 230V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.08V (2.65%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 20.08V (8.73%)
Voltage at Load223.9 VLine Loss: 1977.8 W
Max Power & Breaker74.75 kW350A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 350m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 3245.67 V (1411.16%) | 0.0 V | 5353.83 V (2327.75%) | 1054841.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1947.4 V (846.7%) | 0.0 V | 3212.3 V (1396.65%) | 632905.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1217.12 V (529.18%) | 0.0 V | 2007.69 V (872.91%) | 395565.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 811.42 V (352.79%) | 0.0 V | 1338.46 V (581.94%) | 263710.4 W | Drop High |
| 10 mm² | 57 A | 44 A | 486.85 V (211.67%) | 0.0 V | 803.07 V (349.16%) | 158226.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 304.28 V (132.3%) | 0.0 V | 501.92 V (218.23%) | 98891.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 194.74 V (84.67%) | 35.3 V | 321.23 V (139.67%) | 63290.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 139.1 V (60.48%) | 90.9 V | 229.45 V (99.76%) | 45207.5 W | Drop High |
| 50 mm² | 151 A | 118 A | 97.37 V (42.33%) | 132.6 V | 160.61 V (69.83%) | 31645.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 69.55 V (30.24%) | 160.5 V | 114.72 V (49.88%) | 22603.7 W | Drop High |
| 95 mm² | 232 A | 181 A | 51.25 V (22.28%) | 178.8 V | 84.53 V (36.75%) | 16655.4 W | Drop High |
| 120 mm² | 269 A | 210 A | 40.57 V (17.64%) | 189.4 V | 66.92 V (29.1%) | 13185.5 W | Drop High |
| 150 mm² | 309 A | 241 A | 32.46 V (14.11%) | 197.5 V | 53.54 V (23.28%) | 10548.4 W | Drop High |
| 185 mm² | 353 A | 275 A | 26.32 V (11.44%) | 203.7 V | 43.41 V (18.87%) | 8552.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 20.29 V (8.82%) | 209.7 V | 33.46 V (14.55%) | 6592.8 W | Drop High |
| 300 mm² | 477 A | 372 A | 16.23 V (7.06%) | 213.8 V | 26.77 V (11.64%) | 5274.2 W | Drop High |
| 400 mm² | 570 A | 445 A | 12.17 V (5.29%) | 217.8 V | 20.08 V (8.73%) | 3955.7 W | Drop High |
FAQ — Kabeltværsnit for 325 Ampere ved 350 Meter (230V)
Hvilket kabeltværsnit kræves til 325A ved 350 meter (230V)?
Til 325 Ampere over 350 meter ved 230V anbefales 2× 400 mm² kobberkabel (spændingsfald 6.08V / 2.65%).
Hvor mange kW svarer 325A ved 230V til?
Det svarer til 74.75 kW med en anbefalet sikring på 350A.
Related Lengths & Currents (230V)
325A · 5m (230V)325A · 10m (230V)325A · 15m (230V)325A · 20m (230V)325A · 25m (230V)325A · 30m (230V)325A · 35m (230V)325A · 40m (230V)325A · 45m (230V)325A · 50m (230V)325A · 60m (230V)325A · 70m (230V)10A · 350m (230V)16A · 350m (230V)20A · 350m (230V)25A · 350m (230V)32A · 350m (230V)40A · 350m (230V)50A · 350m (230V)63A · 350m (230V)80A · 350m (230V)100A · 350m (230V)125A · 350m (230V)160A · 350m (230V)200A · 350m (230V)