⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 350 Ampere ved 70 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 350 A over 70 m ved 230V.

Copper Cable (≤3% Drop)185 mm²Drop: 5.67V (2.46%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 5.77V (2.51%)
Voltage at Load224.3 VLine Loss: 1983.8 W
Max Power & Breaker80.5 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A699.07 V (303.94%)0.0 V1153.13 V (501.36%)244673.3 WDrop High
2.5 mm²24 A18 A419.44 V (182.37%)0.0 V691.88 V (300.82%)146804.0 WDrop High
4 mm²32 A25 A262.15 V (113.98%)0.0 V432.43 V (188.01%)91752.5 WDrop High
6 mm²41 A32 A174.77 V (75.99%)55.2 V288.28 V (125.34%)61168.3 WDrop High
10 mm²57 A44 A104.86 V (45.59%)125.1 V172.97 V (75.2%)36701.0 WDrop High
16 mm²76 A59 A65.54 V (28.49%)164.5 V108.11 V (47.0%)22938.1 WDrop High
25 mm²101 A78 A41.94 V (18.24%)188.1 V69.19 V (30.08%)14680.4 WDrop High
35 mm²125 A97 A29.96 V (13.03%)200.0 V49.42 V (21.49%)10486.0 WDrop High
50 mm²151 A118 A20.97 V (9.12%)209.0 V34.59 V (15.04%)7340.2 WDrop High
70 mm²192 A150 A14.98 V (6.51%)215.0 V24.71 V (10.74%)5243.0 WDrop High
95 mm²232 A181 A11.04 V (4.8%)219.0 V18.21 V (7.92%)3863.3 WDrop High
120 mm²269 A210 A8.74 V (3.8%)221.3 V14.41 V (6.27%)3058.4 WDrop High
150 mm²309 A241 A6.99 V (3.04%)223.0 V11.53 V (5.01%)2446.7 WDrop High
185 mm²353 A275 A5.67 V (2.46%)224.3 V9.35 V (4.07%)1983.8 W✓ OK (≤3%)
240 mm²415 A324 A4.37 V (1.9%)225.6 V7.21 V (3.13%)1529.2 W✓ OK (≤3%)
300 mm²477 A372 A3.5 V (1.52%)226.5 V5.77 V (2.51%)1223.4 W✓ OK (≤3%)
400 mm²570 A445 A2.62 V (1.14%)227.4 V4.32 V (1.88%)917.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 350 Ampere ved 70 Meter (230V)

Hvilket kabeltværsnit kræves til 350A ved 70 meter (230V)?

Til 350 Ampere over 70 meter ved 230V anbefales 185 mm² kobberkabel (spændingsfald 5.67V / 2.46%).

Hvor mange kW svarer 350A ved 230V til?

Det svarer til 80.5 kW med en anbefalet sikring på 350A.