Kabeltværsnit for 450 Ampere ved 35 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 450 A over 35 m ved 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.25V (0.98%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.78V (1.21%)
Voltage at Load227.8 VLine Loss: 1011.1 W
Max Power & Breaker103.5 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A449.4 V (195.39%)0.0 V741.3 V (322.3%)202230.0 WDrop High
2.5 mm²24 A18 A269.64 V (117.23%)0.0 V444.78 V (193.38%)121338.0 WDrop High
4 mm²32 A25 A168.53 V (73.27%)61.5 V277.99 V (120.86%)75836.2 WDrop High
6 mm²41 A32 A112.35 V (48.85%)117.6 V185.32 V (80.58%)50557.5 WDrop High
10 mm²57 A44 A67.41 V (29.31%)162.6 V111.2 V (48.35%)30334.5 WDrop High
16 mm²76 A59 A42.13 V (18.32%)187.9 V69.5 V (30.22%)18959.1 WDrop High
25 mm²101 A78 A26.96 V (11.72%)203.0 V44.48 V (19.34%)12133.8 WDrop High
35 mm²125 A97 A19.26 V (8.37%)210.7 V31.77 V (13.81%)8667.0 WDrop High
50 mm²151 A118 A13.48 V (5.86%)216.5 V22.24 V (9.67%)6066.9 WDrop High
70 mm²192 A150 A9.63 V (4.19%)220.4 V15.88 V (6.91%)4333.5 WDrop High
95 mm²232 A181 A7.1 V (3.09%)222.9 V11.7 V (5.09%)3193.1 WDrop High
120 mm²269 A210 A5.62 V (2.44%)224.4 V9.27 V (4.03%)2527.9 WDrop High
150 mm²309 A241 A4.49 V (1.95%)225.5 V7.41 V (3.22%)2022.3 WDrop High
185 mm²353 A275 A3.64 V (1.58%)226.4 V6.01 V (2.61%)1639.7 WDrop High
240 mm²415 A324 A2.81 V (1.22%)227.2 V4.63 V (2.01%)1263.9 WDrop High
300 mm²477 A372 A2.25 V (0.98%)227.8 V3.71 V (1.61%)1011.1 W✓ OK (≤3%)
400 mm²570 A445 A1.69 V (0.73%)228.3 V2.78 V (1.21%)758.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 450 Ampere ved 35 Meter (230V)

Hvilket kabeltværsnit kræves til 450A ved 35 meter (230V)?

Til 450 Ampere over 35 meter ved 230V anbefales 300 mm² kobberkabel (spændingsfald 2.25V / 0.98%).

Hvor mange kW svarer 450A ved 230V til?

Det svarer til 103.5 kW med en anbefalet sikring på 450A.