Kabeltværsnit for 550 Ampere ved 200 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 550 A over 200 m ved 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 10.19V (2.55%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.81V (4.2%)
Voltage at Load389.8 VLine Loss: 9710.2 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2718.17 V (679.54%)0.0 V4483.7 V (1120.93%)2589400.0 WDrop High
2.5 mm²24 A18 A1630.9 V (407.72%)0.0 V2690.22 V (672.56%)1553640.0 WDrop High
4 mm²32 A25 A1019.31 V (254.83%)0.0 V1681.39 V (420.35%)971025.0 WDrop High
6 mm²41 A32 A679.54 V (169.89%)0.0 V1120.93 V (280.23%)647350.0 WDrop High
10 mm²57 A44 A407.72 V (101.93%)0.0 V672.56 V (168.14%)388410.0 WDrop High
16 mm²76 A59 A254.83 V (63.71%)145.2 V420.35 V (105.09%)242756.2 WDrop High
25 mm²101 A78 A163.09 V (40.77%)236.9 V269.02 V (67.26%)155364.0 WDrop High
35 mm²125 A97 A116.49 V (29.12%)283.5 V192.16 V (48.04%)110974.3 WDrop High
50 mm²151 A118 A81.54 V (20.39%)318.5 V134.51 V (33.63%)77682.0 WDrop High
70 mm²192 A150 A58.25 V (14.56%)341.8 V96.08 V (24.02%)55487.1 WDrop High
95 mm²232 A181 A42.92 V (10.73%)357.1 V70.8 V (17.7%)40885.3 WDrop High
120 mm²269 A210 A33.98 V (8.49%)366.0 V56.05 V (14.01%)32367.5 WDrop High
150 mm²309 A241 A27.18 V (6.8%)372.8 V44.84 V (11.21%)25894.0 WDrop High
185 mm²353 A275 A22.04 V (5.51%)378.0 V36.35 V (9.09%)20995.1 WDrop High
240 mm²415 A324 A16.99 V (4.25%)383.0 V28.02 V (7.01%)16183.7 WDrop High
300 mm²477 A372 A13.59 V (3.4%)386.4 V22.42 V (5.6%)12947.0 WDrop High
400 mm²570 A445 A10.19 V (2.55%)389.8 V16.81 V (4.2%)9710.2 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 550 Ampere ved 200 Meter (400V)

Hvilket kabeltværsnit kræves til 550A ved 200 meter (400V)?

Til 550 Ampere over 200 meter ved 400V anbefales 400 mm² kobberkabel (spændingsfald 10.19V / 2.55%).

Hvor mange kW svarer 550A ved 400V til?

Det svarer til 381.05 kW med en anbefalet sikring på 600A.