Kabeltværsnit for 60 Ampere ved 35 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 60 A over 35 m ved 230V.
Copper Cable (≤3% Drop)16 mm²Drop: 5.62V (2.44%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 5.93V (2.58%)
Voltage at Load224.4 VLine Loss: 337.1 W
Max Power & Breaker13.8 kW60A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 59.92 V (26.05%) | 170.1 V | 98.84 V (42.97%) | 3595.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 35.95 V (15.63%) | 194.0 V | 59.3 V (25.78%) | 2157.1 W | Drop High |
| 4 mm² | 32 A | 25 A | 22.47 V (9.77%) | 207.5 V | 37.06 V (16.12%) | 1348.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 14.98 V (6.51%) | 215.0 V | 24.71 V (10.74%) | 898.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 8.99 V (3.91%) | 221.0 V | 14.83 V (6.45%) | 539.3 W | Drop High |
| 16 mm² | 76 A | 59 A | 5.62 V (2.44%) | 224.4 V | 9.27 V (4.03%) | 337.1 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 3.6 V (1.56%) | 226.4 V | 5.93 V (2.58%) | 215.7 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 2.57 V (1.12%) | 227.4 V | 4.24 V (1.84%) | 154.1 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.8 V (0.78%) | 228.2 V | 2.97 V (1.29%) | 107.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.28 V (0.56%) | 228.7 V | 2.12 V (0.92%) | 77.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.95 V (0.41%) | 229.1 V | 1.56 V (0.68%) | 56.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.75 V (0.33%) | 229.3 V | 1.24 V (0.54%) | 44.9 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.6 V (0.26%) | 229.4 V | 0.99 V (0.43%) | 36.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.49 V (0.21%) | 229.5 V | 0.8 V (0.35%) | 29.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.37 V (0.16%) | 229.6 V | 0.62 V (0.27%) | 22.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.3 V (0.13%) | 229.7 V | 0.49 V (0.21%) | 18.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.22 V (0.1%) | 229.8 V | 0.37 V (0.16%) | 13.5 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 60 Ampere ved 35 Meter (230V)
Hvilket kabeltværsnit kræves til 60A ved 35 meter (230V)?
Til 60 Ampere over 35 meter ved 230V anbefales 16 mm² kobberkabel (spændingsfald 5.62V / 2.44%).
Hvor mange kW svarer 60A ved 230V til?
Det svarer til 13.8 kW med en anbefalet sikring på 60A.
Related Lengths & Currents (230V)
60A · 5m (230V)60A · 10m (230V)60A · 15m (230V)60A · 20m (230V)60A · 25m (230V)60A · 30m (230V)60A · 40m (230V)60A · 45m (230V)60A · 50m (230V)60A · 60m (230V)60A · 70m (230V)10A · 35m (230V)16A · 35m (230V)20A · 35m (230V)25A · 35m (230V)32A · 35m (230V)40A · 35m (230V)50A · 35m (230V)63A · 35m (230V)80A · 35m (230V)100A · 35m (230V)125A · 35m (230V)160A · 35m (230V)200A · 35m (230V)