Kabeltværsnit for 600 Ampere ved 45 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 600 A over 45 m ved 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.25V (0.32%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.13V (1.03%)
Voltage at Load398.8 VLine Loss: 1300.0 W
Max Power & Breaker415.69 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A667.19 V (166.8%)0.0 V1100.55 V (275.14%)693360.0 WDrop High
2.5 mm²24 A18 A400.31 V (100.08%)0.0 V660.33 V (165.08%)416016.0 WDrop High
4 mm²32 A25 A250.19 V (62.55%)149.8 V412.7 V (103.18%)260010.0 WDrop High
6 mm²41 A32 A166.8 V (41.7%)233.2 V275.14 V (68.78%)173340.0 WDrop High
10 mm²57 A44 A100.08 V (25.02%)299.9 V165.08 V (41.27%)104004.0 WDrop High
16 mm²76 A59 A62.55 V (15.64%)337.5 V103.18 V (25.79%)65002.5 WDrop High
25 mm²101 A78 A40.03 V (10.01%)360.0 V66.03 V (16.51%)41601.6 WDrop High
35 mm²125 A97 A28.59 V (7.15%)371.4 V47.17 V (11.79%)29715.4 WDrop High
50 mm²151 A118 A20.02 V (5.0%)380.0 V33.02 V (8.25%)20800.8 WDrop High
70 mm²192 A150 A14.3 V (3.57%)385.7 V23.58 V (5.9%)14857.7 WDrop High
95 mm²232 A181 A10.53 V (2.63%)389.5 V17.38 V (4.34%)10947.8 WDrop High
120 mm²269 A210 A8.34 V (2.08%)391.7 V13.76 V (3.44%)8667.0 WDrop High
150 mm²309 A241 A6.67 V (1.67%)393.3 V11.01 V (2.75%)6933.6 WDrop High
185 mm²353 A275 A5.41 V (1.35%)394.6 V8.92 V (2.23%)5621.8 WDrop High
240 mm²415 A324 A4.17 V (1.04%)395.8 V6.88 V (1.72%)4333.5 WDrop High
300 mm²477 A372 A3.34 V (0.83%)396.7 V5.5 V (1.38%)3466.8 WDrop High
400 mm²570 A445 A2.5 V (0.63%)397.5 V4.13 V (1.03%)2600.1 WDrop High

FAQ — Kabeltværsnit for 600 Ampere ved 45 Meter (400V)

Hvilket kabeltværsnit kræves til 600A ved 45 meter (400V)?

Til 600 Ampere over 45 meter ved 400V anbefales 2× 400 mm² kobberkabel (spændingsfald 1.25V / 0.32%).

Hvor mange kW svarer 600A ved 400V til?

Det svarer til 415.69 kW med en anbefalet sikring på 600A.