Kabeltværsnit for 650 Ampere ved 45 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 650 A over 45 m ved 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.35V (0.34%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.47V (1.12%)
Voltage at Load398.6 VLine Loss: 1525.8 W
Max Power & Breaker450.33 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A722.78 V (180.7%)0.0 V1192.26 V (298.06%)813735.0 WDrop High
2.5 mm²24 A18 A433.67 V (108.42%)0.0 V715.35 V (178.84%)488241.0 WDrop High
4 mm²32 A25 A271.04 V (67.76%)129.0 V447.1 V (111.77%)305150.6 WDrop High
6 mm²41 A32 A180.7 V (45.17%)219.3 V298.06 V (74.52%)203433.8 WDrop High
10 mm²57 A44 A108.42 V (27.1%)291.6 V178.84 V (44.71%)122060.2 WDrop High
16 mm²76 A59 A67.76 V (16.94%)332.2 V111.77 V (27.94%)76287.7 WDrop High
25 mm²101 A78 A43.37 V (10.84%)356.6 V71.54 V (17.88%)48824.1 WDrop High
35 mm²125 A97 A30.98 V (7.74%)369.0 V51.1 V (12.77%)34874.4 WDrop High
50 mm²151 A118 A21.68 V (5.42%)378.3 V35.77 V (8.94%)24412.0 WDrop High
70 mm²192 A150 A15.49 V (3.87%)384.5 V25.55 V (6.39%)17437.2 WDrop High
95 mm²232 A181 A11.41 V (2.85%)388.6 V18.83 V (4.71%)12848.4 WDrop High
120 mm²269 A210 A9.03 V (2.26%)391.0 V14.9 V (3.73%)10171.7 WDrop High
150 mm²309 A241 A7.23 V (1.81%)392.8 V11.92 V (2.98%)8137.3 WDrop High
185 mm²353 A275 A5.86 V (1.47%)394.1 V9.67 V (2.42%)6597.9 WDrop High
240 mm²415 A324 A4.52 V (1.13%)395.5 V7.45 V (1.86%)5085.8 WDrop High
300 mm²477 A372 A3.61 V (0.9%)396.4 V5.96 V (1.49%)4068.7 WDrop High
400 mm²570 A445 A2.71 V (0.68%)397.3 V4.47 V (1.12%)3051.5 WDrop High

FAQ — Kabeltværsnit for 650 Ampere ved 45 Meter (400V)

Hvilket kabeltværsnit kræves til 650A ved 45 meter (400V)?

Til 650 Ampere over 45 meter ved 400V anbefales 2× 400 mm² kobberkabel (spændingsfald 1.35V / 0.34%).

Hvor mange kW svarer 650A ved 400V til?

Det svarer til 450.33 kW med en anbefalet sikring på 700A.