Kabeltværsnit for 700 Ampere ved 200 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 700 A over 200 m ved 230V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 4.99V (2.17%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 24.71V (10.74%)
Voltage at Load225.0 VLine Loss: 3495.3 W
Max Power & Breaker161.0 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3994.67 V (1736.81%)0.0 V6589.33 V (2864.93%)2796266.7 WDrop High
2.5 mm²24 A18 A2396.8 V (1042.09%)0.0 V3953.6 V (1718.96%)1677760.0 WDrop High
4 mm²32 A25 A1498.0 V (651.3%)0.0 V2471.0 V (1074.35%)1048600.0 WDrop High
6 mm²41 A32 A998.67 V (434.2%)0.0 V1647.33 V (716.23%)699066.7 WDrop High
10 mm²57 A44 A599.2 V (260.52%)0.0 V988.4 V (429.74%)419440.0 WDrop High
16 mm²76 A59 A374.5 V (162.83%)0.0 V617.75 V (268.59%)262150.0 WDrop High
25 mm²101 A78 A239.68 V (104.21%)0.0 V395.36 V (171.9%)167776.0 WDrop High
35 mm²125 A97 A171.2 V (74.43%)58.8 V282.4 V (122.78%)119840.0 WDrop High
50 mm²151 A118 A119.84 V (52.1%)110.2 V197.68 V (85.95%)83888.0 WDrop High
70 mm²192 A150 A85.6 V (37.22%)144.4 V141.2 V (61.39%)59920.0 WDrop High
95 mm²232 A181 A63.07 V (27.42%)166.9 V104.04 V (45.24%)44151.6 WDrop High
120 mm²269 A210 A49.93 V (21.71%)180.1 V82.37 V (35.81%)34953.3 WDrop High
150 mm²309 A241 A39.95 V (17.37%)190.1 V65.89 V (28.65%)27962.7 WDrop High
185 mm²353 A275 A32.39 V (14.08%)197.6 V53.43 V (23.23%)22672.4 WDrop High
240 mm²415 A324 A24.97 V (10.86%)205.0 V41.18 V (17.91%)17476.7 WDrop High
300 mm²477 A372 A19.97 V (8.68%)210.0 V32.95 V (14.32%)13981.3 WDrop High
400 mm²570 A445 A14.98 V (6.51%)215.0 V24.71 V (10.74%)10486.0 WDrop High

FAQ — Kabeltværsnit for 700 Ampere ved 200 Meter (230V)

Hvilket kabeltværsnit kræves til 700A ved 200 meter (230V)?

Til 700 Ampere over 200 meter ved 230V anbefales 3× 400 mm² kobberkabel (spændingsfald 4.99V / 2.17%).

Hvor mange kW svarer 700A ved 230V til?

Det svarer til 161.0 kW med en anbefalet sikring på 700A.