Kabeltværsnit for 750 Ampere ved 350 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 750 A over 350 m ved 400V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 8.11V (2.03%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 40.12V (10.03%)
Voltage at Load391.9 VLine Loss: 10532.8 W
Max Power & Breaker519.62 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6486.53 V (1621.63%)0.0 V10699.74 V (2674.94%)8426250.0 WDrop High
2.5 mm²24 A18 A3891.92 V (972.98%)0.0 V6419.85 V (1604.96%)5055750.0 WDrop High
4 mm²32 A25 A2432.45 V (608.11%)0.0 V4012.4 V (1003.1%)3159843.7 WDrop High
6 mm²41 A32 A1621.63 V (405.41%)0.0 V2674.94 V (668.73%)2106562.5 WDrop High
10 mm²57 A44 A972.98 V (243.24%)0.0 V1604.96 V (401.24%)1263937.5 WDrop High
16 mm²76 A59 A608.11 V (152.03%)0.0 V1003.1 V (250.78%)789960.9 WDrop High
25 mm²101 A78 A389.19 V (97.3%)10.8 V641.98 V (160.5%)505575.0 WDrop High
35 mm²125 A97 A277.99 V (69.5%)122.0 V458.56 V (114.64%)361125.0 WDrop High
50 mm²151 A118 A194.6 V (48.65%)205.4 V320.99 V (80.25%)252787.5 WDrop High
70 mm²192 A150 A139.0 V (34.75%)261.0 V229.28 V (57.32%)180562.5 WDrop High
95 mm²232 A181 A102.42 V (25.6%)297.6 V168.94 V (42.24%)133046.1 WDrop High
120 mm²269 A210 A81.08 V (20.27%)318.9 V133.75 V (33.44%)105328.1 WDrop High
150 mm²309 A241 A64.87 V (16.22%)335.1 V107.0 V (26.75%)84262.5 WDrop High
185 mm²353 A275 A52.59 V (13.15%)347.4 V86.75 V (21.69%)68320.9 WDrop High
240 mm²415 A324 A40.54 V (10.14%)359.5 V66.87 V (16.72%)52664.1 WDrop High
300 mm²477 A372 A32.43 V (8.11%)367.6 V53.5 V (13.37%)42131.2 WDrop High
400 mm²570 A445 A24.32 V (6.08%)375.7 V40.12 V (10.03%)31598.4 WDrop High

FAQ — Kabeltværsnit for 750 Ampere ved 350 Meter (400V)

Hvilket kabeltværsnit kræves til 750A ved 350 meter (400V)?

Til 750 Ampere over 350 meter ved 400V anbefales 3× 400 mm² kobberkabel (spændingsfald 8.11V / 2.03%).

Hvor mange kW svarer 750A ved 400V til?

Det svarer til 519.62 kW med en anbefalet sikring på 800A.